5-124
T60 Transformer Protection System
GE Multilin
5.5 FLEXLOGIC™
5 SETTINGS
5
ELEMENT:
Breaker control
BREAKER 1 OFF CMD
BREAKER 1 ON CMD
BREAKER 1
Φ
A BAD ST
BREAKER 1
Φ
A INTERM
BREAKER 1
Φ
A CLSD
BREAKER 1
Φ
A OPEN
BREAKER 1
Φ
B BAD ST
BREAKER 1
Φ
A INTERM
BREAKER 1
Φ
B CLSD
BREAKER 1
Φ
B OPEN
BREAKER 1
Φ
C BAD ST
BREAKER 1
Φ
A INTERM
BREAKER 1
Φ
C CLSD
BREAKER 1
Φ
C OPEN
BREAKER 1 BAD STATUS
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
Breaker 1 open command initiated
Breaker 1 close command initiated
Breaker 1 phase A bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase A is closed
Breaker 1 phase A is open
Breaker 1 phase B bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase B is closed
Breaker 1 phase B is open
Breaker 1 phase C bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase C is closed
Breaker 1 phase C is open
Breaker 1 bad status is detected on any pole
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
BREAKER 2 to 6
Same set of operands as shown for BREAKER 1
ELEMENT:
Digital counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Digital counter 1 output is ‘more than’ comparison value
Digital counter 1 output is ‘equal to’ comparison value
Digital counter 1 output is ‘less than’ comparison value
Counter 2 to 8
Same set of operands as shown for Counter 1
ELEMENT:
Digital elements
Dig Element 1 PKP
Dig Element 1 OP
Dig Element 1 DPO
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Dig Element 2 to 48
Same set of operands as shown for Dig Element 1
ELEMENT:
FlexElements™
FxE 1 PKP
FxE 1 OP
FxE 1 DPO
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
FxE 2 to 16
Same set of operands as shown for FxE 1
ELEMENT:
Ground distance
GND DIST Z1 PKP
GND DIST Z1 OP
GND DIST Z1 OP A
GND DIST Z1 OP B
GND DIST Z1 OP C
GND DIST Z1 PKP A
GND DIST Z1 PKP B
GND DIST Z1 PKP C
GND DIST Z1 SUPN IN
GND DIST Z1 DPO A
GND DIST Z1 DPO B
GND DIST Z1 DPO C
GND DIST Z2 DIR SUPN
Ground distance zone 1 has picked up
Ground distance zone 1 has operated
Ground distance zone 1 phase A has operated
Ground distance zone 1 phase B has operated
Ground distance zone 1 phase C has operated
Ground distance zone 1 phase A has picked up
Ground distance zone 1 phase B has picked up
Ground distance zone 1 phase C has picked up
Ground distance zone 1 neutral is supervising
Ground distance zone 1 phase A has dropped out
Ground distance zone 1 phase B has dropped out
Ground distance zone 1 phase C has dropped out
Ground distance zone 2 directional is supervising
GND DIST Z2 to 3
Same set of operands as shown for GND DIST Z1
ELEMENT:
Ground
instantaneous
overcurrent
GROUND IOC1 PKP
GROUND IOC1 OP
GROUND IOC1 DPO
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
GROUND IOC2 to 12
Same set of operands as shown for GROUND IOC 1
ELEMENT:
Ground time
overcurrent
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
GROUND TOC2 to 6
Same set of operands as shown for GROUND TOC1
Table 5–11: T60 FLEXLOGIC™ OPERANDS (Sheet 2 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...