7-2
T60 Transformer Protection System
GE Multilin
7.1 COMMANDS
7 COMMANDS AND TARGETS
7
7.1.3 CLEAR RECORDS
PATH: COMMANDS
CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
The
CLEAR ALL RELAY RECORDS
command does not clear the
XFMR LIFE LOST
(transformer loss of life) value.
7.1.4 SET DATE AND TIME
PATH: COMMANDS
SET DATE AND TIME
The date and time can be entered here via the faceplate keypad only if the IRIG-B or SNTP signal is not in use. The time
setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com-
mand. The new time will take effect at the moment the ENTER key is clicked.
COMMANDS
CLEAR RECORDS
CLEAR USER FAULT
REPORTS? No
Range: No, Yes
CLEAR EVENT RECORDS?
No
Range: No, Yes
CLEAR OSCILLOGRAPHY?
No
Range: No, Yes
CLEAR DATA LOGGER?
No
Range: No, Yes
CLEAR BREAKER 1
ARCING AMPS? No
Range: No, Yes
CLEAR BREAKER 2
ARCING AMPS? No
Range: No, Yes
CLEAR DEMAND
RECORDS?: No
Range: No, Yes
CLEAR ENERGY?
No
Range: No, Yes
CLEAR UNAUTHORIZED
ACCESS? No
Range: No, Yes
CLEAR DIRECT I/O
COUNTERS? No
Range: No, Yes. Valid only for units with Direct Input/
Output module.
CLEAR PMU 1 RECORDS?
No
Range: No, Yes
CLEAR PMU 1 CONFIG
CHANGE COUNTER? No
Range: No, Yes
CLEAR LOSS OF LIFE
RECORDS? No
Range: No, Yes
CLEAR TELEPROTECT
COUNTERS? No
Range: No, Yes
CLEAR ALL RELAY
RECORDS? No
Range: No, Yes
COMMANDS
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
(YYYY/MM/DD HH:MM:SS)
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...