8.2 SETTINGS SECURITY
8 SECURITY
8
4.
Verify one more time that you wish to remove the template by clicking
Yes
.
The EnerVista software will remove all template information and all settings will be available.
8.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS
The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.
a) LOCKING FLEXLOGIC™ EQUATION ENTRIES
The following procedure describes how to lock individual entries of a FlexLogic™ equation.
1.
Right-click the settings file or online device and select the
Template Mode > Create Template
item to enable the set-
tings template feature.
2.
Select the
FlexLogic > FlexLogic Equation Editor
settings menu item.
By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon on
the upper right of the window will also indicate that EnerVista UR Setup is in
EDIT mode
.
3.
Specify which entries to lock by clicking on them.
The locked entries will be displayed against a grey background as shown in the example below.
Figure 8–7: LOCKING FLEXLOGIC™ ENTRIES IN EDIT MODE
4.
Click on
Save
to save and apply changes to the settings template.
5.
Select the
Template Mode > View In Template Mode
option to view the template.
6.
Apply a password to the template then click
OK
to secure the FlexLogic™ equation.
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...