GE Multilin
T60 Transformer Protection System
8-15
8 SECURITY
8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM
8
8.3ENERVISTA SECURITY MANAGEMENT SYSTEM
8.3.1 OVERVIEW
The EnerVista security management system is a role-based access control (RBAC) system that allows a security adminis-
trator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by
multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The
EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista soft-
ware after installation. It is recommended that security be enabled before placing the device in service.
8.3.2 ENABLING THE SECURITY MANAGEMENT SYSTEM
The EnerVista security management system is disabled by default. This allows access to the device immediately after
installation. When security is disabled, all users are granted administrator access.
1.
Select the
Security > User Management
menu item to open the user management configuration window.
2.
Check the
Enable Security
box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password
upon starting the software.
8.3.3 ADDING A NEW USER
The following pre-requisites are required to add new users to the EnerVista security management system.
•
The user adding the new user must have administrator rights.
•
The EnerVista security management system must be enabled.
The following procedure describes how to add new users.
1.
Select the
Security > User Management
menu item to open the user management configuration window.
2.
Enter a username in the
User
field. The username must be between 4 and 20 characters in length.
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...