3-14
T60 Transformer Protection System
GE Multilin
3.2 WIRING
3 HARDWARE
3
3.2.5 PROCESS BUS MODULES
The T60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
•
Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the T60 by reducing the number of individual copper terminations.
•
Integrates seamlessly with existing T60 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
•
Communicates using open standard IEC 61850 messaging.
For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual.
3.2.6 CONTACT INPUTS AND OUTPUTS
Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The T60 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
If the inputs must be isolated per row, then two inputs per common return should be selected (4D module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when there is a voltage across open contact (the detector allows a current of about 1 to 2.5 mA), and the current monitor
is set to “On = 1” when the current flowing through the closed contact exceeds about 80 to 100 mA. The voltage monitor is
intended to check the health of the overall trip circuit, and the current monitor can be used to seal-in the output contact until
an external contact has interrupted current flow. If enabled, the current monitoring can be used as a seal-in signal to ensure
that the form-A contact does not attempt to break the energized inductive coil circuit and weld the output contacts.
Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs. Form-A
contact output with or without a current or voltage monitoring option is not polarity sensitive. The polarity shown in the figure
is required for solid-state contact output connection.
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...