March 2004
4-2
Configuring Meter Data
Entering Base (Zero)
and Span Output
Values
The
4-20 Loop
submenu enables you to enter the information needed
to set up output parameters: unit type, base (zero) and span values,
and error handling. To enter data in the
4-20 Loop
submenu:
1.
Press [ESC]. The UTX878 enters the
User Program.
2.
Press the [
X
] key until
CONFIG
is bracketed and press [ENT].
3.
Press [
T
] to reach the
4-20 Loop
submenu, and press [ENT].
Entering Output Type
and Units
1.
In the
Loop
submenu, press [ENT] to enter the
Units
option.
2.
The menu displays five options: Channel 1, Channel 2, AVG,
SUM and DIFF. Use the [
S
] and [
T
] keys to scroll to the desired
option, and press [ENT].
Note:
Channel 2, AVG, SUM and DIFF are only available for a two-
channel UTX878.
3.
The screen now displays three measurement parameters: velocity,
volumetric, and soundspeed. Scroll to the desired selection and
press [ENT].
4.
The menu now asks for the unit type.
•
For velocity or soundspeed measurements, the menu offers a
single selection (either feet/sec or meters/sec, depending on
your choice of units). Press [ENT] to confirm the entry and
return to the previous menu.
•
For volumetric, the menu offers a list of output units (either
metric or English). Scroll to the desired units and press [ENT].
Press [ESC] until you return to the
CONFIG
menu.
Summary of Contents for UTX878 Ultrasonic
Page 2: ...iii March 2004 The UTX878 Flow Transmitter and Transducers ...
Page 8: ...Chapter 1 ...
Page 20: ...March 2004 Installation 1 11 Figure 1 5 UTX878 Outline and Installation Dwg 712 1196 rev 2 ...
Page 22: ...March 2004 Installation 1 13 Figure 1 7 UTX878 Wiring Diagram Dwg 702 528 rev 2 ...
Page 23: ...Chapter 2 ...
Page 45: ...Chapter 3 ...
Page 52: ...Chapter 4 ...
Page 60: ...Chapter 5 ...
Page 65: ...Chapter 6 ...
Page 75: ...Chapter 7 ...
Page 80: ...Appendix A ...
Page 85: ...Appendix B ...
Page 86: ...CE Mark Compliance Introduction B 1 EMC Compliance B 1 ...
Page 88: ...Appendix C ...
Page 89: ...Data Records Site Data C 1 ...
Page 93: ...Appendix D ...
Page 94: ...Service Record Introduction D 1 Data Entry D 1 Diagnostic Parameters D 3 ...