A-2
VersaMax PROFINET Scanner Manual
– December 2013
GFK-2721A
A
Technical Data
API:
Single API (0) used.
Number of Application Relations
supported:
1 AR or 1SR-AR Set made of 2 SR-ARs
Maximum length of cyclic input
data:
1440 bytes
Maximum length of output data:
1440 bytes
Alarm Types:
Diagnostic, Return of Submodule, Plug, Pull
DCP:
Get/Set/Identify supported. Only All, Name Of Station,
and Station Name Alias filters supported
Identification & Maintenance:
I&M0 only
Context Management:
by CL-RPC
Minimum cycle time:
1ms
Ethernet rate:
100 Mbit/s full duplex with auto-negotiation
Limitations
The following features are
not supported
in release 2.00.
RT over UDP
IRT
Multicast communication
DHCP
DCP Hello service
DNS (Domain Name Service protocol)
FastStartUp
Supervisor-AR. Note: Supervisor-DA-AR
is
supported. (Device Access supported)
Optical power diagnostics (IC200PNS002)
CBA
Substitute DataOnly one Input-CR and one Output-CR are supported.