GFK-2721A
Chapter 1 Introduction
1-3
1
VersaMax PROFINET Scanner Versions
The PNS network interface module is available in two versions to allow you to use the network
media that meets the requirements of your application.
IC200PNS001: Two 10/100 Mbps shielded copper RJ-45 media connectors
IC200PNS002: Two 100Mbps SC
–Duplex fiber optic media connectors
PNS001
PWR1 (L)
PWR2 (R)
OK
FAULT
CONNECT
LAN
PORT 1 (L)
PORT 2 (R)
MAINT
COMM
!
The PROFINET Scanner supports the use of either one or two power supplies. Use of the
second power supply is optional. Power supplies mount directly onto the module and latch into
place. The illustration above shows the PROFINET Scanner with no power supplies installed.
Note:
For redundancy applications (MRP and Hot Standby CPU redundancy), it is
recommended that each VersaMax PNS be installed and configured with dual
power supplies.