9.5
Time-tick Contacts
There are four time-tick contacts. They can be used to provide regular pulses of power
flow to other program functions. The four time-tick contacts have time durations of 0.01
second, 0.1 second, 1.0 second, and 1 minute.
The state of these contacts does not change during the execution of the sweep. These
contacts provide a pulse having an equal on and off time duration.
The contacts are referenced as T_10MS (0.01 second), T_100MS (0.1 second), T_SEC
(1.0 second), and T_MIN (1 minute).
The following timing diagram represents the on/off time duration of these contacts.
X
X/2
SEC
T XXXXX
X/2
SEC
SEC
These time-tick contacts represent specific locations in %S memory.
122
GFK-1503E
VersaMax PLC User Manual
For public disclosure