4.8
Ethernet Connection for CPUE05
The Ethernet port on PLC module IC200CPUE05 connects directly to a 10BaseT (twisted
pair shielded) network without an external transceiver. Connect the port to an external
10BaseT hub or switch or a hub or repeater with autosense of 10/100 using a twisted pair
cable. Cables are readily available from commercial distributors. GE recommends
purchasing rather than making cables. Your 10BaseT twisted pair shielded cables must
meet the applicable IEEE 802 standards.
4.8.1
Network Connection
Connection of the CPUE05 to a 10BaseT network is shown below:
10BaseT
Twisted Pair
Cable
10BaseT Hub
To
Other Network
Devices
CPUE05
The cable between each node and a hub or repeater can be up to 100 meters in length.
Typical hubs or repeaters support 4 to 12 nodes connected in a star wiring topology.
Ethernet Cable
Series 90-70 PLC with
Ethernet Interface
Host Computer or Control Device
Running a Host Communications
Toolkit Application
Series 90-30 PLC with
Ethernet Interface
Programmer Software
running on a PC
VersaMax PLC with
CPUE05
VersaMax PLC with
CPUE05
Hub
Installation
GFK-1503E User Manual 67
For public disclosure
Summary of Contents for VersaMax PLC
Page 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 317: ......