Name
Description
Default
Range
crsp_tout
Transfer/Response timeout value (in
seconds)
16 (0010H)
10 – 3600 (0e10H)
fflush
ARP cache timeout interval (in seconds)
0 – 604800 (93a80H)
600 (0258H)
gctl_port
UDP port for Ethernet Global Data control
messages
7937 (1f01H)
0-65535 (ffffH)
gdata_port
UDP port for point-to-point Ethernet Global
Data messages
18246 (4746H)
0-65535 (ffffH)
gbcast_ttl
IP time-to-live for global broadcast messages
(hop count)
1 (1H)
0-255 (00ffH)
gucast_ttl
IP time-to-live for point-to-point messages
(hop count)
16 (10H)
0-255 (00ffH)
gXX_udp
UDP port for host group XX
18246 (4746H)
0-65535 (ffffH)
gXX_ttl
IP time-to-live for host group (multicast)
messages (hop count)
1 (1H)
0-255 (00ffH)
gXX_addr
IP group address for host group XX (must be
class D address)
224.0.7.XX
224.0.0.2 -
239.255.255.255
ittl
IP header default time-to-live (hop count)
64 (0040H)
0-255 (00ffH)
ifrag_tmr
IP fragment timeout interval (in seconds)
3 (0003H)
0-65535 (ffffH)
wnodelay
TCP nodelay option (0=inactive, 1=active)
0 (000H)
0,1
wkal_idle
TCP keepalive timer value (in seconds)
240 (00f0H) = 4.0
minutes
0-65535 (ffffH)
wkal_cnt
TCP keepalive probe count
2 (0002H)
wkal_intvl
TCP keepalive probe interval (in seconds)
60 (003cH)
wmsl
TCP maximum segment lifetime (in seconds)
30 (001eH)
wsnd_buf
TCP send buffer size in bytes
4096 (1000H)
0-32767 (7fffH)
wrcv_buf
TCP receive buffer size in bytes
4096 (1000H)
nmin_poll1
NTP min. poll interval for host 1. The value
specifies log(2) of the interval in seconds (eg:
the value 3 means 8 secs, 4 means 16 sec,
etc)
6 (0006H) = 64 seconds
4 – 14 (000eH)
nmax_poll1
NTP maximum poll interval for host 1 (in log
(2) of seconds)
10 (000aH) = 1024 sec.
(16 – 16384 sec)
nmin_poll2
NTP min. poll interval for host 2 (in log(2) of
seconds)
6 (0006H) = 64 sec.
nmax_poll2
NTP max. poll interval for host 2 (in log(2) of
seconds)
10 (000aH) = 1024 sec.
nmin_poll3
NTP min. poll interval for host 3 (in log(2) of
seconds)
6 (0006H) = 64 sec.
nmax_poll3
NTP max. poll interval for host 3 (in log(2) of
seconds)
10 (000aH) = 1024 sec.
90
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Summary of Contents for VersaMax PLC
Page 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 317: ......