13.6.2
Unexpected Ethernet Restart or Runtime
Errors
Sustained heavy EGD and/or SRTP operation can exceed the data transfer and processing
capacity of the CPUE05. This can result in missed EGD exchanges, unexpected automatic
restarts of the Ethernet interface within the CPUE05, or runtime fatal errors at the
Ethernet interface.
Restart errors are indicated in the PLC Fault Table as one or more of the following:
Loss of daughterboard
(no exception Event)
Reset of daughterboard
(no exception Event)
LAN system-software fault; restarted LAN I/F
with exception Event = 3, Entry 2 = 1,
Entry 3 = 5f0fH
After any of the above errors, the Ethernet interface restarts itself automatically without
manual intervention.
The above Ethernet restarts may be accompanied by one or more of the following in the
PLC Fault Table:
Backplane communications with PC fault; lost request
(no exception event)
LAN system-software fault; resuming
with exception Event = 28, Entry 2 = 1, SCode = 95255037H
Runtime errors suspend normal operation and a blink fatal error code in amber at the
STAT LED. To recover, manually restart the Ethernet interface. Runtime error codes
31
and
33
have been observed under heavy load. Refer to the section,
earlier in this chapter for descriptions of runtime diagnostic fatal error codes.
All Ethernet Global Data (EGD) exchanges default to status code 18 (0012H) during a
loss or reset of the Ethernet interface. EGD operation will resume after the restart is
complete.
These restart and runtime errors occur when the CPUE05 cannot process the attempted
volume of EGD and/or SRTP requests. As these errors have been observed only when the
CPUE05 is connected to a repeater-type network hub, the primary remedy is to replace
the repeater-type hub with a switching-type network hub. A secondary remedy is to
reduce the number, size, or frequency of the EGD exchanges and/or transfers over SRTP
connections.
270
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Summary of Contents for VersaMax PLC
Page 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 317: ......