Previously-configured Module Installed After Autoconfiguration
: If a module
that was previously-configured but missing at powerup is installed-after powerup, the
CPU generates an addition of module diagnostic and the module is added back into the
I/O scan.
All Modules Removed After Autoconfiguration
: If all modules are absent at
powerup, the CPU clears the configuration. This allows modules to be inserted and added
to the configuration at the next powerup.
5.4.3
Diagnostic Message Summary
addition of module
A module is present at powerup but not configured. It is added to the configuration.
Autoconfiguration is enabled and the module is capable of being autoconfigured.
addition of module
A previously-configured module is inserted after powerup. The CPU resumes scanning of the module.
configuration
mismatch
A module was found at or after powerup that does not match the configuration for that slot.
extra module
1. A module is present at powerup but not configured.
2. Autoconfiguration is not enabled.
3. A previously-unconfigured module is inserted after powerup.
loss of module
A configured module is missing during powerup or normal operation.
addition of rack
1.
An Expansion Receiver Module that was not previously configured is present during
configuration.
2.
During normal operation, communication is restored with a previously missing or failed
Expansion Receiver Module. The CPU starts scanning I/O for the modules in that rack. “Addition of
Module” faults are not generated when scanning resumes. However, if communications cannot be
restored with any modules in the rack, “Loss of Module” faults are generated.
loss of rack
1.
A previously configured Expansion Receiver Module is not present during configuration.
2.
During normal operation, a previously working Expansion Receiver Module stops working.
Modules in the same expansion rack are terminated.
extra rack
A previously-unconfigured Expansion Receiver module is inserted after powerup. Modules in the
expansion rack are ignored.
Expansion
Transmitter
mismatch
1. An Expansion Transmitter Module (IC200ETM001) is present but not configured.
2. An Expansion Transmitter Module (IC200ETM001) is configured but not present.
expansion bus
speed change
The expansion bus speed automatically calculated by the CPU during autoconfiguration has changed.
unsupported
feature
A module is present that is not supported by the CPU.
80
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Summary of Contents for VersaMax PLC
Page 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Page 317: ......