2
Key Features
1.
Padlock provision on the breaker escutcheon to
lock the breaker in the open and trip-free position
2.
Optional operations counter (field installable)
3.
Trip unit visible through the breaker escutcheon
— metering and trip information accessible
without opening the cubicle door
4.
Choice of three trip units — Power+™, MicroVersaTrip
Plus™ or MicroVersaTrip PM™
5.
Power Management Ready — breaker can be pre-wired
for power management trip unit (MVT-PM) —
upgrading is as simple as changing the trip unit
6.
Flush mounted manual charging handle provided
on both manually operated and electrically operated
breakers
7.
Field-installable accessories — shunt trip, bell alarm
(shown), auxiliary switch, undervoltage device,
electrical lockout device, “hidden-on” (limited
access) button, secondary disconnect(s), remote
close accessory, CLOSE and TRIP push button covers
(sealable), remote charge indicator switch
8.
Sealable door over the trip unit — trip settings can be
viewed but not changed
9.
Easy access to key breaker operating information —
drawout position indicator, breaker contact status, closing
spring status all visible from the front of the breaker
10. Manual close button (“limited access” option on
electrically operated breakers)
11. Dedicated secondary disconnect points — up to 72
connection points available to accommodate all breaker
accessories, including power management and neutral
sensor (see breaker wiring diagram on pages 30 and 31)
12. Expanded auxiliary switch option — 4 stage or 7 stage
13. “One-shot” electronic close circuit (not shown)
14. Breaker rating nameplate with 15 digit catalog number.
Catalog number completely describes breaker ratings,
trip unit type and characteristics, breaker operation
and control voltages, and all accessories with associated
ratings.
5
2
1
6
7
8
9
10
12
11
3, 4, 5
14