background image

EXHAUSTING THE DRYER (cont.)

Installation Instructions

BEFORE YOU BEGIN

 

Remove and discard existing plastic or metal foil 

duct and replace with UL-listed duct.

 

Remove any lint from the wall exhaust opening.

Internal 

Duct 

Opening

Wall

Check that exhaust 

hood damper opens 

and closes freely.

STANDARD REAR EXHAUST

We recommend that you install your dryer before 

installing your washer. This will permit direct 

access for easier exhaust connection.

Slide the end of the exhaust duct on the back of the 

dryer and secure with duct tape or a hose clamp.

NOTE:

 We strongly recommend using rigid metal 

exhaust duct.

 

For straight-line installation, connect the dryer 

exhaust to the wall, using duct tape.

RECOMMENDED CONFIGURATION TO 

MINIMIZE EXHAUST BLOCKAGE

Using duct elbows will prevent duct kinking and 

collapsing.

Duct

Transition 

Ducting

Wall Side

Dryer 

Side

14

EXHAUST SYSTEM CHECKLIST

HOOD OR WALL CAP

 

Terminate in a manner to prevent back drafts or entry 

of birds or other wildlife.

 

Termination should present minimal resistance to 

the exhaust airflow and should require little or no 

maintenance to prevent clogging.

 

Wall caps must be installed at least 12” above ground 

level or any other obstruction with the opening 

pointed down.

 

Never vent the dryer out of the roof.

SEPARATION OF TURNS

 

For best performance, separate all turns by at least 

4 ft. of straight duct, including distance between last 

turn and dampened wall cap. 

SEALING OF JOINTS

 

All joints should be tight to avoid leaks. The male end 

of each section of duct must point away from the 

dryer.

 

Duct joints should be made air- and moisture-tight 

by wrapping the overlapped joints with duct tape or 

aluminum tape.

 

Do not assemble ductwork with any fasteners 

that extend into the duct. These fasteners can 

accumulate lint, creating a potential fire hazard.

 

Horizontal runs should slope down towards the 

outdoors 1/4” per foot.

 

Provide an access for inspection and cleaning of 

the exhaust system, especially at turns and joints. 

Exhaust system shall be inspected and cleaned at 

least once a year.

INSULATION

 

Ductwork that runs through an unheated area or is 

near air conditioning should be insulated to reduce 

condensation and lint buildup.

Summary of Contents for WX9X2

Page 1: ...s dryer installation must be performed by a qualified installer Install the clothes dryer according to these instructions and local codes DO NOT install a clothes dryer with flexible plastic venting m...

Page 2: ...at 800 626 2002 during normal business hours Part Number Accessory WE25M53 Complete Kit hoses Y adapter washers included OR WE1M847 Long Hose and WE1M848 Short Hose PM14X10056 Dryer door opening vent...

Page 3: ...o the dryer room See the sections for electrical connection information If the dryer is approved for installation in an alcove or closet it will be stated on a label on the dryer back The dryer MUST b...

Page 4: ...ng to one male end of the Y connector Tighten by hand until firmly seated 5 Ensure the rubber flat washer is in place and attach the dryer s long inlet hose to the other male end of the Y connector Ti...

Page 5: ...er cord is unplugged from the wall Turn the dryer s gas shut off valve in the supply line to the OFF position Disconnect and discard old flexible gas connector and ducting material Shut off Valve MATE...

Page 6: ...t be adjusted for operation at or below 2000 ft elevation For operation at elevations above 2000 ft input ratings should be reduced at a rate of 4 percent for each 1000 ft above sea level Installation...

Page 7: ...f valve F Apply pipe compound or PTFE tape to all male threads Shut Off Valve Plugged Tapping CONNECTING THE DRYER TO THE GAS SUPPLY Install a female 3 8 NPT elbow at the end of the dryer gas inlet In...

Page 8: ...l Code CSA C22 1 This appliance must be supplied with 120V 60Hz and be connected to a properly grounded branch circuit protected by a 15 or 20 amp circuit breaker or time delay fuse If electrical supp...

Page 9: ...OFF THE TERMINAL BLOCK Slip joint pliers Flat blade crewdriver Phillips screwdriver Level TOOLS YOU WILL NEED MATERIALS YOU WILL NEED 4 dia metal elbow 3 4 strain relief UL recognized 4 duct clamps 2...

Page 10: ...re or electrical shock GROUNDING INSTRUCTIONS For a grounded cord connected dryer This dryer must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shoc...

Page 11: ...120 240V 30A power supply cord kit marked for use with dryers and provided with closed loop or spade terminals with upturned ends not supplied Hot Wire Hot Wire Green Wire Relocatre green ground screw...

Page 12: ...l length of flexible metal duct should not exceed 7 9 2 4 m For many applications installing elbows at both the dryer and the wall is highly recommended see illustrations at right Elbows allow the dry...

Page 13: ...s all the straight portions and elbows of the system transition duct included EXHAUST LENGTH 13 DO NOT bend or collapse ducting Use elbows if turns are necessary DO NOT use excessive exhaust length Cu...

Page 14: ...uld present minimal resistance to the exhaust airflow and should require little or no maintenance to prevent clogging Wall caps must be installed at least 12 above ground level or any other obstructio...

Page 15: ...LBOW AND DUCT FOR EXHAUST TO LEFT OR RIGHT SIDE OF CABINET Preassemble 4 elbow with 4 duct Wrap duct tape around joint QVHUW GXFW DVVHPEO HOERZ UVW WKURXJK WKH side opening and connect the elbow to th...

Page 16: ...safety hazard 16 DUCT TAPE ADDING ELBOW FOR EXHAUST THROUGH BOTTOM OF CABINET Insert the elbow through the rear opening and connect it to the dryer internal duct Apply duct tape as shown on the joint...

Page 17: ...ndio La instalaci n de la secadora debe efectuarla un instalador calificado Instale la secadora de ropa de acuerdo con estas instrucciones y en cumplimiento con los c digos locales NO instale una seca...

Page 18: ...ndo al 800 626 2002 durante el horario comercial habitual N mero de Pieza Accesorio WE25M53 Kit Completo mangueras lavadora con adaptador en Y incluido O WE1M847 Manguera Larga y WE1M848 Manguera Cort...

Page 19: ...instalaci n de su secadora en alcoba o armario esto figurar en una etiqueta en el reverso de la secadora Esta secadora DEBE tener una ventilaci n al exterior Ver la secci n SALIDA AL EXTERIOR DE LA SE...

Page 20: ...e a mano hasta que est firmemente asentada 5 Aseg rese de que la arandela plana de goma se encuentre en su lugar y sujete la manguera larga de entrada de la secadora al otro extremo macho del conector...

Page 21: ...riente Gire a la posici n OFF apagado la v lvula de gas de la secadora de la l nea de suministro Desconecte y elimine el conector flexible de gas y el material del conducto V lvula de cierre MATERIALE...

Page 22: ...N Los niveles de entrada de las secadoras de ropa a gas est n basados en el funcionamiento al nivel de mar y no necesitan ajustes para funcionar en o por debajo de los 2000 pies de elevaci n Para un...

Page 23: ...en todas las roscas macho V lvula de apagado Toma a rosca C MO CONECTAR LA SECADORA AL SUMINISTRO DE GAS Instale un codo hembra NPT de 3 8 al final de la entrada de gas de la secadora Instale un adap...

Page 24: ...utilice una llama abierta para detectar p rdidas de gas Controle todas las conexiones con una soluci n jabonosa o un elemento equivalente Aplique una soluci n jabonosa La soluci n para controlar p rdi...

Page 25: ...el tomacorriente de la vivienda antes de comprar el cable 4 Placa de cubierta Kit WE1M454 C MO CONECTAR UNA SECADORA ELECTRICA S ltese si se trata de las secadoras a gas o si su secadora ya tiene un...

Page 26: ...STRUCCIONES DE CONEXI N A TIERRA Para una secadora conectada con cable con conexi n a tierra Esta secadora deber estar conectado a tierra En caso de mal funcionamiento o aver a la conexi n a tierra re...

Page 27: ...tores de cobre 10 AWG m nimo o kit de cable de suministro de energ a de 120 240V 30A marcado para su uso con secadoras y provisto con terminales de bucle cerrado o hembra con extremos hacia arriba no...

Page 28: ...tos La longitud total del conducto de metal flexible no deber superar los 7 9 2 4 m Para muchas aplicaciones se recomienda enf ticamente la instalaci n de codos tanto en la secadora como en la pared L...

Page 29: ...de escape incluye todas las porciones rectas y todos los codos del sistema incluyendo el ducto de transici n LONGITUD DE SALIDA NO doble o pliegue los conductos Utilice codos si algunos codos resultan...

Page 30: ...ia m nima al flujo de salida y debe requerir poco mantenimiento para evitar las obstrucciones Las cubiertas de pared deben instalarse por lo menos a 12 sobre el nivel del suelo o cualquier otra obstru...

Page 31: ...Cierre la abertura trasera con la placa protectora Kit WE1M454 Desconecte la secadora del suministro el ctrico Use guantes y protectores para brazos Si esto no se cumple se podr producir una incendio...

Page 32: ...nte Introduzca el codo a trav s de la abertura trasera y con ctelo al conducto interno de la secadora Aplique cinta aislante como puede verse en la junta entre el conducto interno de la secadora y el...

Reviews: