54
09665
-01
.2
01
9-
Gb
13
Installation of all shut-off valves and blind flanges
Position in
parts list
Parts list position: 2060, 2070, 232
Tools: Spanner SW 17, allen key 6 mm
Working course
230, 210
2060
233, 232,
231
- Put in the suction filter with the gasket
- Install the shut-off valves (on the discharge and suction side) with gaskets and screws
- Install the blind flange with O-ring and screws
- Tighten all screws
12 I Assembly of compressor
INFO
Observe tightening torques!
Use screws of correct length for the installation of the intermediate flanges!
60 Nm
60 Nm
60 Nm