Fig. 19
4.7 Laying suction and discharge lines
A rule of thumb:
Always lay the first pipe section starting from the shut-off valve
downwards
and parallel to the drive shaft.
ATTENTION
Improperly installed pipes can cause cracks and tears, the result
being a loss of refrigerant.
INFO
Proper layout of the suction and discharge lines directly after
the compressor is integral to the system’s smooth running and
vibration behaviour.
Important:
- Start unloader may only be employed during the starting phase.
- Check the solenoid valve and the non-return valve regularly for tightness.
- In addition, we recommend to use a heat protection thermostat on the discharge side of the com-
pressor. This protects the compressor against thermal overloading. Connect the heat protection
thermostat in series on the safety chain of the control circuit, to switch off the compressor if
necessary.
- Follow these instructions to avoid thermal overloading.
Fig. 18
Solenoid valve dead
Non-return valve open
Rigid
fixed point
As short as possible
4
|
Compressor assembly