7
|
Electrical connection
400 V
Direktstart YY
Teilwicklungsstart Y/YY
1V1
1W1
1U1
2W1
2V1
2U1
L3
L2
L1
L3
L2
L1
L3
L2
L1
1V1
1W1
1U1
2W1
2V1
2U1
Direct start YY
Part winding start Y/YY
The motor is wired for direct start (YY) at the factory. For part winding start Y / YY, the bridges must
be removed and the motor feed line connected according to the circuit diagram:
ATTENTION
Failure to do this results in opposed rotary fields and results in
damage to the motor. After the motor starts up via partial winding
1, partial winding 2 must be switched on after a maximum delay
of one second . Failure to comply can adversely affect the service
life of the motor.