18
09704-06.2016-DGbFIT
rCn
D
GB
F
I
TR
CN
6.1 Preparation
6.2 Work to be carried out
6
|
Maintenance
FK50 / ...
460 N, TK
555 N, TK
660 N, TK
775 N, TK
830 N
980 N
460 K, 555 K
660 K, 775 K
830 K, 980 K
Designation
Art. No.
Art. No.
Art. No.
Set of gaskets
80231
80089
Valve plate kit
80243
80244
08926
Set of shaft seals
80023
Oil SP 46, 1 litre
02279
Oil SE 55, 1 litre
02282
Oil change:
In principle, an oil change is not mandatory if the system is correctly manufactured
and operated. However, based on decades of experience we recommend that the following oil
change/service work is carried out:
-
First oil change during the first maintenance of the vehicle.
-
Then after every 5,000 operating hours, though no more than 3 years, clean the oil strainer
at the same time. If necessary, also empty the oil reservoir at the shaft seal.
Annual checks:
Oil level, tightness of the compressor, running noise, pressures, temperatures,
function of auxiliary devices such as checking the capacity control.
The valves are fundamentally maintenance-free.
However, constant leakage can occur after repeated blowing off due to abnormal operating conditions.
This leads to reduced performance and increases the compressed gas temperature. In this case check
the valves and replace as necessary.
6.4 Integrated decompression valves
Only use genuine GEA spare parts!
6.3 Recommended spare parts
WARNING! Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.