be found in the "Product Information" (bare compressor) and in case of a
package, the package lay out drawing.
Hint!
If an oil rectifier system is applied in the refrigeration system, the oil
return line must be connected to the oil return connection (see
"Product Information").
Suspension of system pipework
To eliminate vibration transmission to the system piping, the following is
recommended:
•
Install all piping free of tension.
•
Secure the piping by clips or brackets in two directions.
•
Install (stop) valves, piping and accessories such, that there is no load
exerted on the compressor.
Recommendation
Fig.9
To ensure quick and easy maintenance work, the following is
recommended;
1.
In all situations, install a removable section of pipe (>= 200
mm) on the suction flange of the compressor
2.
In case oil separator is not mounted onto the package,
install a removable section of pipe (>= 200 mm) on the
discharge flange of the compressor
1.3.6.1 Torques for factory supplied check valve / stop valve assembly
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
0089288_imm_v_english_19
22
07.04.2021