GENERAL INFO
Main setup data
Description
Value
Remark
Grasso V 300 (T) .. V 600 (T)
Grasso V 700 (T) .. V 1800 (T)
General limits of operation
Caution!
Refer to Product Information Section 4.2, Page 51
Start frequency
max. 6 starts per hour
The
NO-solenoid has to be
de-energised 20 seconds
after starting the compressor
motor to enabel the motor to
reach the minimum speed and
the compressor to develop the
required oil pressure.
Time interval between stopping
and re-starting
min. 2 minutes
Time interval between starting
and re-starting
min. 10 minutes
Time interval between loading
and unloading
min. 3 minutes
For continuous minimum part-
load (i.e. more than 30
minutes) consult Grasso.
Adjust the steps between up
and down loading, in such a
way that the system is running
stable.
Oil level
25-75% crankcase sight glass
Control oil pressure
suction pr 8 bar (g)
Lubricating oil pressure
difference
between 1.3 and 4.5 bar Setting approx. 2.0 bar (g)
After a mimimum of 15 minutes
running time at an oil
temperature of approx. 50
o
C
Superheat
>0 K
Oil discharge -
running in -
filter
Factory mounted;
to be replaced after max. 100 running hours
by “normal” oil discharge filter
element
Oil discharge filter
Supplied loose; replacement for factory mounted running in filter
0089288_imm_v_english_19
07.04.2021
9