PRODUCT INFORMATION
LIQUID CHILLER GRASSO DX R
200 ... 1600
_601011_pi_dxr_gbr_1_.doc
31
DX chiller type RR 1000
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
1134
216
966
211
845
206
782
203
723
199
614
192
518
187
38
1103
251
954
241
821
232
760
228
701
225
595
219
502
214
Cooling medium
outlet temperature
at condenser (°C)
45
1082
269
936
260
804
252
744
249
687
245
583
239
490
230
DX chiller type RR 1200
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
1406
268
1198
262
1048
256
970
251
896
247
762
238
643
232
38
1368
311
1183
298
1018
288
942
283
870
279
738
271
622
265
Cooling medium
outlet temperature
at condenser (°C)
45
1342
334
1160
322
997
313
922
308
852
304
722
297
608
285
DX chiller type RR 1600
Secondary refrigerant outlet temperature at evaporator (°C)
Refrigerating capacity in kW
Driving capacity in kW
10 6 2 0 -2 -6 -10
32
1812
334
1547
320
1356
320
1256
314
1162
308
988
298
834
290
38
1758
387
1524
373
1313
360
1216
354
1124
349
955
340
805
331
Cooling medium
outlet temperature
at condenser (°C)
45
1722
427
1492
402
1285
390
1189
385
1099
380
933
371
786
362
Summary of Contents for Grasso DX 600
Page 1: ..._601011_pi_dxr_gbr_1_ doc 1 Liquid Chiller Grasso DX R 200 1600 Product Information ...
Page 4: ......
Page 6: ......
Page 44: ......