PRODUCT INFORMATION
LIQUID CHILLER GRASSO DX R
200 ... 1600
36
_601011_pi_dxr_gbr_1_.doc
Analog inputs
All process variables are processed in analogue mode.
Sensor inputs are designed for standadized input signal (4 - 20) mA.
Digital inputs
Suitable for 24 V DC.
Analog outputs
Control slide position as non-floating signal (4 - 20) mA.
Digital outputs
Floating contacts for signal transfer to L. V. Switching Station and Master Control.
All solenoid valves are designed for 24 V DC.
Field of application
No maritime or airborne applications.
Maritime application on request.
Controled variable
Process temperature in °C (Standard: evaporating temperature or temperature of secondary refrigerant.)
Controlled by a three-position controller.
Set point and neutral zone can be parameter.
Set point adjustment
Setpoints can be adjusted through the unit controller by a higher-level master control using analog signal (4 - 20)
mA.
Start-up modes
MANUAL
SC unit/ chiller is switched ON / OFF manually, independently of the refrigerating
demand.
AUTO
SC unit/ chiller is switched ON / OFF automatically depending on local refrigerating
demand.
Operating modes
MANUAL
Manual key-operated capacity control (the control slide is shifted manually).
AUTO
Automatic setpoint-dependent capacity control (the control slide is shifted
automatically).
Control modes
LOCAL
SC unit/ chiller can be operate independently (no master control).
CENTRAL
SC unit/ chiller is controlled by master control only.