GRASSO SYSTEM CONTROL
Kap.6 - 6
638660E_chapter6.doc
01.2003/0
6.3
Description and diagnosis of alarm messages
Display message / Explanation
Possible cause of the alarm
Alarm clearance
The level in the refrigerant
separator is too high.
Reduce the level in the refrigerant
separator.
004 Alarm
Evaporator
refrigerant level
too high
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
The level sensor is defective.
Replace the level sensor.
This alarm is activated if the input
signal E 1.1 ‘Separator liquid level’
equals 0.
The digital input module defective.
Replace the digital input module.
Gas alarm system is active.
Reset the gas alarm system.
005 Alarm
Refrigerant leak
detected
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
This alarm is activated if the input
signal E 1.2 ‘Gas sensor’ equals 0.
The digital input module defective.
Replace the digital input module.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
009 Alarm
Wire failure
oil separator
temperatur
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the oil separator
temperature sensor.
The analogue input module
defective.
Replace the analogue input module.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
010 Alarm
Wire failure
external temperature
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the external
temperature sensor.
The analogue input module
defective.
Replace the analogue input module.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
011 Alarm
Wire failure
external set point
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the external set
point sensor.
The analogue input module
defective.
Replace the analogue input module.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......