Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
Kap.6 - 10
638660E_chapter6.doc
01.2003/0
Display message / Explanation
Possible cause of the alarm
Alarm clearance
The discharge pressure is too high.
Remove cause of high discharge
pressure in the refrigeration plant.
060 Alarm
(01)
Discharge
pressure
too high
‘Pdis hi alarm’ limit is set too low.
Change ‘Pdis hi alarm’ limit to a
suitable value.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This alarm is activated if the
discharge pressure exceeds the ’Pdis
hi alarm’ limit value.
The sensor is defective.
Replace the sensor.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
061 Alarm
(01)
Wire failure
discharge pressure
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the discharge
pressure sensor.
The analogue input module
defective.
Replace the analogue input module.
The intermediate pressure is too
high.
Remove cause of high intermediate
pressure in the refrigeration plant.
062 Alarm
(01)
Intermediate
pressure
too high
‘Pint hi alm n1/2’ limit is set too
low.
Change ‘Pint hi alm n1/2’ limit to a
suitable value.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This alarm is activated if the
intermediate pressure exceeds the
’Pint hi alm n1/2’ limit value.
Note:
the actual motor speed (n) is
of relevance for which limit is active.
The sensor is defective.
Replace the sensor.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
063 Alarm
(01)
Wire failure
intermediate pressure
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the intermediate
pressure sensor.
The analogue input module
defective.
Replace the analogue input module.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
064 Alarm
(01)
Wire failure
oil pressure
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the oil pressure
sensor.
The analogue input module
defective.
Replace the analogue input module.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......