Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/0
638660E_chapter6.doc
Kap.6 - 17
Warning message
Possible cause
Warning clearance
044 Warning
Selection not
permitted. Please
check input data.
This warning is activated if a
selection has been made or an
entery has been entered that is not
permitted.
The selection or entered data is not
permitted in combination with
other selections and/or data.
Certain selections and/or data
involved will be changed
automatically in such a way that a
valid condition is created.
MPI / Profibus-DP cable broken or
plug-in connector defective.
Replace the defective parts.
045 Warning
MPI / Profibus-DP
network comm.
failure
The master PLC operation mode
state is ’STOP’.
Change the PLC operation mode
into ‘RUN’.
The ‘Life-bit’ of the slave is not
returned by the master.
Check the master PLC program.
This warning is activated at the slave
GSC if an operation mode has been
activated, where data exchange via
MPI or Profibus-DP is activated, and
the slave GSC is not connected to
the master.
Wrong selection of the ’Netw fault’
parameter in the operating mode
menu.
Select the correct setting for the
’Netw fault’ parameter.
The suction gas overheat is too
low.
Remove the cause of low suction
gas overheat in the refrigeration
plant.
097 Warning
(01)
Low suction
gas overheat
’Suct dif temp’ plus ’Low warning’
set too high.
Change ’Suct dif temp’ and ’Low
warning’ limits to suitable values.
’dTo alarm dly’ time is set too
short.
Change ’dTo alarm dly’ time to a
suitable value.
This warning is activated if the
suction gas overheat is less than
’Suct dif temp’ plus ’Low warning’
limit values and the ½ time delay
’dTo alarm dly’ has expired.
The configuration is incorrect.
Check the parameter ‘Refrigerant’
and ‘Comp type’ in the
configuration menu.
The compressor discharge
temperature is too high.
Remove the cause for high
discharge temperature in the
refrigerating plant.
098 Warning
(01)
High discharge
temperature
‘Tdis hi alarm‘ minus ‘High
warning‘ set too high.
Change ‘Tdis hi alarm’ and ‘High
warning’ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
discharge temperature is higher than
the ‘Tdis hi alarm’ minus ‘High
warning’ limit values.
The sensor is defective.
Replace the sensor.
The compressor intermediate
temperature at the low pressure
side is too high.
Remove the cause for high
intermediate temperature LP in the
refrigerating plant.
099 Warning
(01)
High intermediate
temperature (LP)
‘Tdis hi alarm‘ minus ‘High
warning‘ set too high.
Change ‘Tdis hi alarm’ and ‘High
warning’ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
intermediate temperature LP is
higher than the ‘Tdis hi alarm’ minus
‘High warning’ limit values.
The sensor is defective.
Replace the sensor.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......