GRASSO SYSTEM CONTROL
01
.200
4
/
1
638660E_chapter2.doc Chap. 2 - 7
2.5.3
Switching off sequence in the normal case and in case of an alarm with ’Pump down’
Stop command
Output — compressor motor on
Decrease of capacity
Minimum capacity reached
’Pump down’ timer active
Stop pressure reached
Alarm generated
Figure 2.8, Switching off sequence in the normal case (A) and in case of an alarm (B)
with ’ Pump down’
A
Normal case:
As soon as the minimum capacity and the stop pressure are reached the
capacity control solenoids are de-energised and the compressor motor
is stopped.
B
In case of an alarm:
As soon as the ’Pump down’ timer has expired the capacity control solenoids
are de-energised and the compressor motor is stopped.
•
If
(1)
Stop command
→
Then
(3)
Decrease of capacity
→
Then
(5)
’Pump down’ timer active
•
If
(4)
Minimum capacity reached
and
(6)
Stop pressure reached
→
Then
Reset the actuating signals (2) and (3)
or
•
If
(4)
Minimum capacity reached
and
(5)
’Pump down’ timer expired
→
Then
(7)
Generate alarm
→
Then
Reset the actuating signals (2) and (3)
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......