2.7.2.8
Low external temperature alarm (Chiller outlet temperature)
In case of Chiller application this alarm is used as frost protection of the evaporator.
The low external temperature alarm function is illustrated in the following diagram.
T
ext
External temperature
A..
Time characteristic of the external
temperature
V..
Forced reduction of the capacity
due too low external temperature
B..
Low external temperature
limitation active
T..
Limit timer active; After that this
timer has expired the capacity
control is enabled again and the
compressor capacity can be
increased.
b..
Limit value for disabling capacity
increase
f..
Limit value for forced reduction of
capacity
W..
Warning limit
Al..
Alarm limit
ML W.. Warning active
ML A.. Alarm active
3..
Reset of the active alarm
Figure 2.24, Low external temperature or Chiller outlet temperature alarm
External temp
Text low alarm
Low warning
+
External temp:
Actual external temperature in °C
Text low alarm:
Alarm limit for minimum external temperature in °C
Low warning:
Enter the warning value as an offset to the alarm limit in K
<<
Limit values 01
>>
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......