Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/0
638660E_chapter3.doc
Chap. 3 - 7
3.8
Saving changes
Press
,
Select the main menu 50 “Configuration“.
Press
until the following selection appears on the display:
Configuration
accept
save
( ok)
( ?)
<<
I I
Use the key
“save” to permanently save the configuration on the EPROM of the PLC.
)
With “save” the PLC will go into STOP automatically and after 1 to 2 minutes it goes back into RUN
again. Therefore, this procedure can be performed when the PLC is in RUN only (see 4.3.). Otherwise the
following system message is displayed: “$369 S7 command error 20”.
During this time the GSC cannot respond to any action from the operator.
)
Before the PLC returns to RUN do not press buttons or switch off power! Otherwise the information on
the EPROM will be lost.
3.9
Check the compressor unit’s wiring
•
Remove each compressor unit sensor connector from its sensor and wait for an alarm message to appear. If
a ‘Wire failure’ alarm message does not appear for the disconnected sensor, then this sensor has not been
configured in menu 50 ‘Configuration’.
•
If the alarm message appears even though no connector has been removed, check the wiring to the sensor,
or, if the sensor is not mounted, then make sure it has not been configured.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......