Warning message
Possible cause
Warning clearance
The discharge temperature at the
high pressure side is too high.
Remove cause of high discharge
temperature in the refrigeration
plant.
127 Warning
(01)
Compressor heating
Discharge temperature
(HP) too high
This warning is activated if the
discharge temperature at the high
pressure side exceeds a fixed limit
value.
6.5
No alarm signal and the compressor will not start
Compressor will not start, although there is no active alarm.
Key
„ON“ has been pressed and the LED K1 “ON“ is flashing.
Cause
Remedy
No ‘start release’ signal
The input ´start release´ is not
closed.
Close input or install a link.
‘Auto Start dly’ active
The time setting ‘Auto start dly’ in
‘control menu’ has not yet expired.
Wait until the delay time has
expired.
‘Start to start’ or
‘Stop to start’ delay active
The time settings ‘Start to start’ or
‘Stop to start’ in ‘Timer values’
menu has not yet expired.
Wait until the delay times have
expired.
A warning that disables the
compressor start is still active.
Remove the cause for the warning.
PV < (SP + ½ NZ)
PV= Process value
SP = Set point
NZ= Neutral zone
Check set point and neutral zone
settings in ´Control settings´menu.
Attention!
In case of suction pressure control
the set point value is entered in
degrees Celsius.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......