Areas of application
The compressors are filled at the factory with the following oil type:
FUCHS Reniso Triton SE 55
Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. HG
X
7/2110-4 R134a).
3.1 Refrigerants
• HFKW / HFC: R134a
3.2 Oil charge
ATTENTION! Compressor operation is possible within the operating limits
shown in the diagrams. Please note the significance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.
- Max. permissible discharge end temperature 140 °C
- Max. permissible switching frequency 12x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with additional cooling:
- Use only oils that are highly thermally stable.
- Avoid continuous operation near the limits.
For operation with capacity regulator:
- The suction gas superheat temperature may need to be reduced
or set individually when operating near to the threshold.
For operation with frequency converter:
- The maximum current and power consumption must not be
exceeded. In the case of operation above the mains frequency,
the application limit can therefore be limited.
During operation in the vacuum range, there is a danger of air
entering on the suction side. This can cause chemical reactions,
pressure rise in the condenser and an excessive compressed-gas
temperature. Avoid absolutely any entry of air.
3.3 Limits of application
INFO!
For refilling, we recommend the above oil types.
Alternatives:
see lubricants table, Chapter 7.5.
The oil level must be in the visible
part of the sight glass; damage
to the compressor is possible if
overfilled or underfilled!
ATTENTION!
Fig. 3
max. oil level
min. oil level