background image

 

 

5

 

ISOLATED BEFORE MAINTENANCE WORK IS 
UNDERTAKEN 

Oil Charge 
The compressors are pre charged with Polyolester oil. 
Following initial start-up, some of this oil will migrate to 
other areas of the system. Ensure the oil charge in the 
system is adequate as follows :-  

 
The following routine maintenance is required: 
Every 3-6 months 
The condenser should be cleaned with a soft brush to 
ensure correct operation of the condensing unit. When the 
condenser coil is obstructed by dirt or rubbish, the unit will 
experience high condensing temperatures which will result in 
higher running costs, loss of compressor efficiency and 
ultimately overheating of the compressor and/or condenser 
fans. 

• 

N2CQ ‘M’ models utilise an oil balance line between 
compressors, ensure the oil balance line sightglass 
level is 1/2 full when the compressors are not running. 

• 

N2CQ ‘L’ models are fitted with a separator reservoir, 
ensure the oil charge is adequate to show in the upper 
sight glass when the compressors are not running. 

The pressure relief valve should be inspected for any 
pressure release. If a release has occurred or there is a 
requirement by the customer maintenance schedule the 
relief valve should be changed. 

 

Note: on N2CQ ‘M’ models with oil balance lines, the oil 
level may show as empty when only one compressor is 
running, this is normal. The true oil level will show when 
both compressors are running, or both are at rest. 

 

The PRV MUST be changed every 5 years

Only suitable Polyolester oil, such as Mobil EAL  

 

Arctic 22 CC (or equivalent), should be used. 

Every 12 months 

 

Check security of fixings, especially the fan and motor 
mounting. Check refrigerant pipeline for damage and leaks.
Check motor (fans should rotate freely). 

4. OPERATING LIMITS 
The HP/LP switch must be set to prevent the unit from 
operating outside of its application limits. 

Check torque settings of compressor rotalock valves (see 
table below). 

The LP switch and Step Controller must not be set any 
lower than the figures below: 

 

When necessary 

 

R404A & R407C 

Clean the fins, guard and general casework. Care must be 
taken when cleaning the fins to prevent damage. It is 
recommended that a soft brush and mild detergent solution 
be used. 

Maximum HP 

Cut out BarG

Minimum 

SST °C     

R404A 
R407C 

LP Cut out 

BarG 

R407C 

Unit 

Range 

LP Cut out 

BarG R404A 

R404A 
R407C 

High-pressure spray washing of the unit must not be 
undertaken, as damage to fin coatings and components will 
occur. Low-pressure spray washing using specialist coil 
cleaning solutions is recommended. 

NS/NC-

'MX/S' 

-20 2  1.7 

25.2 

NS/NC-
'LX/S/V' 

-40 0.35  N/A 25.2 

 

WARNING! SAFETY GOGGLES MUST BE WORN 
DURING THIS OPERATION. 

SCQ 'M' 

-15 

2.7 

N/A 

25.2 

SCQ 'LX' 

-35 

0.7 

N/A 

25.2 

 

6. INVALIDATION OF GUARANTEE 

 

Searle accepts no liability, according to Searle's terms and 
conditions of sale, for loss or damage arising as a result of: 

R134A 

Maximum HP Cut 

out BarG 

Minimum SST 

°C          

R134a 

LP Cut out BarG 

R134a 

Unit Range 

R134a 

(i)   Failure to install, set up or put to work any part of 

equipment in the manner specified in the I&M 
instructions, or 

'MX/S' -20 

0.37 

14.4 

(ii) 

 Failure to maintain the equipment in the manner 

specified in the I&M instructions, or 

'LX/S/V' -20 

0.37 

14.4 

SCQ 

Not Suitable for use with R134a 

(iii) 

 Replacement parts, additional parts or accessories 

supplied by persons other than Searle having been 
incorporated into, or attached to the equipment, or 

 

The LP differential setting must be set high enough to 
prevent short cycling of the unit. 

(iv)  The equipment having been adapted for use, operated 

or used in such a way as does not conform to Searle's 
recommendations. 

The LP Cut-Out pressure is the LP range setting minus 
the LP differential setting. 

 

 

The HP switch must be set at 0.9 x the PRV setting for all 
refrigerants. As standard units are fitted with a PRV set to 
27.6 BarG, the HP switch must not be set higher than 
25.2 BarG. 

7. Compressor Rotalock Valve Torques 

Discharge Suction 

Unit 

Size Torque  Size  Torque 

For R134a refrigerant a lower pressure 16 BarG PRV is 
available, part number 200-200-528, the HP switch must 
not
 be set any higher than 14.4 BarG. 

SCQ7L & 8L 

N/A 

N/A 

1" x 14 

60 -70 Nm 

SCQ13M to 27M 

 

Multiple Evaporator Applications 

SCQ9L & 14L 

If the condensing unit is connected to multiple 
evaporators operating independently of one another, it is 
essential that the saturated suction temperature remains 
within the operating limits when the minimum number of 
evaporators are running.  

1" x 14 

60 - 70 Nm 

1" x 14 

60 - 70 Nm 

SCQ31M 

NSQ09L to 18L 

60 – 70 

90 – 100 

1" x 14 

1 1/4" x 12 

Nm 

Nm 

NSQ15M to 45M 

If the saturated suction temperature falls close to or below 
the operating limits for medium temperature 'M' units 
when the minimum number of evaporators are running, 
the use of 'L’ units, or other Searle condensing unit 
products should be considered. 

NSQ24L to 40L 

90 – 100 

 100 – 120 

1 1/4" x 12 

1 3/4" x 12 

Nm 

Nm 

NSQ56M to 92M 

NSQ48L 

100 – 120 

 140 – 145 

 1 3/4" x 12

 2 1/4" x 12 

Nm 

Nm  

NSQ110M 

 
5. MAINTENANCE 

Check compressor rotalocks as described in the 
maintenance section ‘Every 12 months’ (p4). 

 
WARNING! THE UNIT MUST BE ELECTRICALLY 

Note:  

connection sizes are the threaded spud connection 

Summary of Contents for Searle NSQ Series

Page 1: ...Pipework to and from the unit should be selected to suit the application and not the connection size of the unit It should be supported independently from the unit and in a way that prevents the tran...

Page 2: ...e Compressor Contactor Each compressor supply is switched via a contactor The contactor is controlled via the Compressor Step Controller and integrates the compressor safety chain of the HP LP s and M...

Page 3: ...er outside of the application limits as shown in section 4 For a full description of controller settings please refer to the table on page 8 g Anti Cycle Delay Start Timer Standard on NSQ NCQ optional...

Page 4: ...l Pressure Relief Valve fitted in the side of the liquid receiver If the unit is not located externally in open air the relief valve outlet must be piped away to open air Regular maintenance is requir...

Page 5: ...ay washing using specialist coil cleaning solutions is recommended NS NC MX S 20 2 1 7 25 2 NS NC LX S V 40 0 35 N A 25 2 WARNING SAFETY GOGGLES MUST BE WORN DURING THIS OPERATION SCQ M 15 2 7 N A 25...

Page 6: ...616 034 200 200 610 NSQ18 3LV C 200 200 175 200 452 118 231 940 106 200 200 409 200 563 040 200 616 034 200 200 610 NDQ18 3LV C 200 200 180 200 452 118 231 940 106 200 200 409 200 563 040 200 616 034...

Page 7: ...200 800 240 200 800 244 216 154 158 200 200 103 44 613 16 AWX NSQ18 3LX C 216 131 010 200 200 744 200 200 741 216 112 317 200 800 240 200 800 244 216 154 158 200 200 103 44 613 16 CWX NSQ18 3LV C 216...

Page 8: ...10 NSQ NDQ EC2 Controller Parameters Units with EC fans and or digital compressor 18 0 0 NSQ E 0 0 0 NCQ E 2 NDQ 0 0 8...

Page 9: ...Q45 3MS C3EI C NDQ Model Type 45 unit size 3 3 phase supply E Unit with Electronic control EC Fans use drawing 44 613 06 XXX W Wiring diagrams for units with AC standard fansets cover all electrical o...

Page 10: ...11a SCQ All Units 1MX A SCQ 611 06 XXX W Single Phase with AC Fans 10...

Page 11: ...11b SCQ All Units 3MX A SCQ 613 06 XXX W Three Phase with AC Fans 11...

Page 12: ...NAL BLOCK WAGO 280 633 1 3 10 218 431 456 ENDPLATE FUSED TERMINAL BLOCK WAGO 1 1 11 218 431 608 TERM END PLATE WAGO 280 314 1 3 12 218 431 616 TERMINAL BLOCK WAGO 249 116 1 4 13 218 431 802 SLOTTED DI...

Page 13: ...12 301 ISOLATOR P1 32 V SVB KLOCKNER 1 1 7 216 112 310 32A ISOLATOR SHAFT EXTENTION KIT 1 1 8 216 131 003 CONTACTOR DILM 9 AMPS 240V COIL N C 1 1 10 216 210 625 20mm 3 15A ANTI SURGE GLASS FUSE 1 1 11...

Page 14: ...11e NSQ NSE15 1MX A 44 611 16 XXX W ZB15 Single Phase with AC Fans 14...

Page 15: ...11f NSQ NSE15 1MX A2 E 44 611 16 XEX W ZB15 Single Phase with EC Fans LARGE CABLE LARGE CABLE SMALL CABLE SMALL CABLE 15...

Page 16: ...11g NSQ NSE19 to 26 1MX A B or C 44 611 06 XXX W ZB19 to ZB26 Single Phase AC Fans 16...

Page 17: ...11h NSQ NSE19 to 26 1MX A B C 2 3 E 44 611 06 XEX W ZB19 to ZB26 Single Phase EC Fans LARGE CABLE LARGE CABLE SMALL CABLE SMALL CABLE 17...

Page 18: ...11i NSQ NSE15 to 45 3MX A B C 44 613 06 XXX W ZB15 to ZB45 Three Phase AC Fans 18...

Page 19: ...11j NSQ NSE15 to 45 3MX S A B C 2 3 E 44 613 06 XEX W ZB15 to ZB45 Three Phase EC Fans NDQ30 to 45 3MX S C 2 3 E ZBD30 to ZBD45 Three Phase EC Fans LARGE CABLE LARGE CABLE SMALL CABLE SMALL CABLE 19...

Page 20: ...11k NDQ 30 to 45 3MX S C 44 613 XDX W ZBD30 to ZBD45 Three Phase AC Fans 20...

Page 21: ...11l NCQ NCE 56 to 110 3MX S D E 2 3 44 633 16 XXX W ZB56 to ZB11 Three Phase AC Fans 21...

Page 22: ...11m NSQ NSE 15 to 30 1MX S A B C 2 3 44 611 ST2 Layout Diagram 22...

Page 23: ...11n NSQ NSE 09 to 18 3LX S 15 to 45 3MX S A B C 2 3 44 613 ST2 Layout Diagram 23...

Page 24: ...11o NCQ NCE 24 to 48 3LX S 56 to 110 3MX S D E 2 3 44 633 3 ST2 Layout Diagram 24...

Page 25: ...12 DIMENSIONS Case A B C 25...

Page 26: ...ESS 4 MOUNTING HOLES FOR M8 FIXING BOLTS SIGHT GLASS VIEWING PORT 80 465 483 80 180 LIQUID SUCTION COMP ACCESS CONTROLS ACCESS 6 MOUNTING HOLES FOR M8 FIXING BOLTS SIGHT GLASS VIEWING PORT 750 FXG CTR...

Page 27: ...18 0 197 1194 2260 600 2x750 570 E NCQ92 3MX E 11 09 25 1 167 4 3 36 7 2 0 48 7 8 1 3 8 18 0 207 1194 2260 600 2x750 570 E NCQ110 3MX E 13 34 29 2 198 4 3 36 7 2 0 48 7 8 1 5 8 18 0 236 1194 2260 600...

Page 28: ...0 40 1 1 2 12 0 19 3 8 7 8 6 2 123 573 1128 505 749 475 A NSE11 3LX A 2 41 6 5 32 1 1 2 12 0 19 3 8 7 8 6 2 122 573 1128 505 749 475 A NSE13 3LX A 2 65 8 0 52 1 1 2 12 0 19 3 8 7 8 6 2 134 573 1128 50...

Reviews: