To adjust the second sensor, the process valve must be moved once to its end
positions by an external solenoid valve.
3.2.3
Control Top with Solenoid Valves
The control top with solenoid valves acts as a control top. The signalling takes
place in the same way as with the control top without solenoid valves. with the
difference being that the solenoid valve integrated in the base is operated in
accordance with the control signals. Depending on the design of the process
valve, up to 3 solenoid valves can be installed in the control top.
To provide compressed air support to the actuator spring, a pneumatic NOT logic
element can be used.
The control signals are given by the user's process control system or by
operating the solenoid valves manually. To do this, use a screwdriver to turn the
screw (S) from 0 to 1, see figure.
Fig.5
3.2.4
Control Top with Cap
Fig.6:
Control Top with Cap
According to protection class IP67 and/or 69k (EN 60529) the control top T.VIS
M-15 is suitable for use in this design and if the electrical and pneumatic
connections are installed correctly.
Observe the general instructions regarding ESD protection.
3.2.5
Safety Air Exhaust/Installation Position
To provide protection against excess pressure which can build up in the inside of
the control top, a vent plug (E2) is fitted in the base.
Description
Functional description
430BAL010697EN_2
20
15.04.2020
Summary of Contents for T.VIS M-15
Page 6: ...430BAL010697EN_2 6 15 04 2020...
Page 53: ...Fig 27 Assembly and installation Electrical connections 430BAL010697EN_2 15 04 2020 53...
Page 55: ...Fig 28 Assembly and installation Electrical connections 430BAL010697EN_2 15 04 2020 55...
Page 119: ...Appendix 430BAL010697EN_2 15 04 2020 119...
Page 120: ......