Connection
Wiring Diagram for 24 V DC Control Systems with N Logic
46
Operating Instructions · Control Top T.VIS
®
M-15
Edition 2017-10-16
NOTE
If electrically isolated circuits are used for valve actuation and feedback, the jumper
between terminal 17 and 18 must be removed. The separate reference potential is then
applied to terminal 17.
Key to wiring diagram for 24 V DC control systems with N logic
Item
Description
WD.1
Interface module T.VIS M-15
Type 24 V DC (material no.: 221-589.53)
WD.2
Proximity switch fitted to lantern
WD.3
T.VIS outputs (PNP-current sinking) without jumper
WD.4
Common L+ selected for solenoid valves
WD.5
Higher-level PLC / I/O level 24VDC
WD.6
24 V DC power supply
WD.7
Earth