Technical data: inputs for solenoid valve activation
Designation
Description
Control voltage
max. 24 V DC (+20 % / -12.5 %)
Current consumption, solenoid valve
35 mA
Technical data: Outputs
Designation
Description
Maximum power rating per feedback
output
50 mA
Voltage drop at the outputs
≤ 3 V
Short circuit and overload protection
yes
Technical data: External initiator
Designation
Description
Design
digital 2-wire configuration (Namur)
Technical data: ambient conditions
Designation
Description
Ambient temperature
-20…+70 °C
Connection terminals for conductor
cross section
up to 1.5 mm²
5.4
Specifications for AS-Interface Adapter Module
Type designation: 221-589.24 AS-I MODUL
Technical data: power supply
Designation
Description
Operating voltage U
BUS
23,5…31.6 V DC
No-load current
≤ 22 mA*
Rated isolation voltage
≤ 0.5 kV
AS-i specification
V3.0 (max. 62 slaves with master
V3.0)
Configuration IO code / ID code / ID2
code
7.A.7.E
Reverse voltage protection
yes
*Observe the operating current for the 24 V DC interface module!
When using an A/B slave with a version 2.0 ASI master, it must be ensured that
parameter P3 = 1 and output DO3 = 0 are set.
Technical data
Specifications for AS-Interface Adapter Module
430BAL010697EN_2
15.04.2020
29
Summary of Contents for T.VIS M-15
Page 6: ...430BAL010697EN_2 6 15 04 2020...
Page 53: ...Fig 27 Assembly and installation Electrical connections 430BAL010697EN_2 15 04 2020 53...
Page 55: ...Fig 28 Assembly and installation Electrical connections 430BAL010697EN_2 15 04 2020 55...
Page 119: ...Appendix 430BAL010697EN_2 15 04 2020 119...
Page 120: ......