Troubleshooting
The operator can perform the following measures to rectify malfunctions:
• clean the actuator plate
• replace the batteries
These measures are described in the operation manual 966.230.00.0.
Malfunction
Cause
Rectification
Incorrect flushes (too soon, too
late, unwanted)
Sensor window dirty or wet
▶ Clean or dry the actuator plate.
→ See operation manual
966.230.00.0.
Sensor window scratched
▶ Replace the actuator plate.
A flush is released without manual
actuation when the user steps
back from the WC.
Automatic flush actuation active
▶ Deactivate automatic flush
actuation.
Water is running continuously into
the WC ceramic appliance.
Software fault
▶ Interrupt the power supply
(mains fuse) for 10 seconds.
Flat gasket for the flush valve
defective
▶ Replace the flat gasket for the
flush valve.
Fill valve defective
▶ Replace the fill valve.
The WC ceramic appliance is not
being flushed out properly.
Flush volumes set incorrectly
▶ Set the correct full flush volume
on the flush valve.
▶ Set the correct partial flush
volume with the Geberit Service
Handy.
Flush cannot be released.
Network failure
▶ Check the power supply (mains
fuse).
Flush cannot be released. The
LED in the sensor window flashes
when a user is in the user
detection range.
Battery capacity low
▶ Change the batteries. → See
operation manual 966.230.00.0.
Flush cannot be released. The
LED in the sensor window lights
up when a user is in the user
detection range.
Batteries flat
▶ Change the batteries. → See
operation manual 966.230.00.0.
Flush cannot be released. The
LED in the sensor window flashes
quickly.
Plug of the lifting device not
plugged in correctly
▶ Correctly plug the plug into the
lifting device.
Lifting device defective
▶ Replace the lifting device.
12
4516380043 © 10-2018
966.335.00.0 (01)