45
GFCI/RCD trips
From
electrical box To spa
Ground
wire
GFCI/RCD
panel
The Y Series packs are equipped with a
GFCI/RCD
tripper circuit in case an HL error occurs.
• Find the GFCI/RCD tripper circuit (J1) on the board
located behind the temperature probe and remove
the jumper
• Reset the GFCI/RCD and see if an error occurs
If HL appears, follow the HL error troubleshooting
chart (in the Troubleshooting section)
• If no error occurs, re-install the jumper
Note: If the GFCI/RCD trips only when jumper (J1) is
installed, replace the spa pack.
From
electrical box
To spa
Important
connections:
Neutral of
GFCI /RCD
must be
connected to
neutral bus.
Neutral from
spa must be
connected to
breaker.
The GFCI/RCD trips and the jumper (J1) is not installed,
the error doesn’t come from the GFCI/RCD tripper
circuit.
• Verify that the GFCI/RCD circuit is properly
connected
• If it's not, reconnect it
• Verify the spa pack wiring (make sure that the neutral
and the ground have not been inverted)
If the GFCI/RCD is properly connected but still tripping,
• Unplug all outputs from the spa pack (pumps, blower,
heater, ozonator etc)
• If it doesn't trip while all outputs are unplugged,
reconnect one output at a time until the GFCI/RCD
trips again
• Replace defective component
GFCI/RCD (J1)
Note: Incorrect GFCI/RCD wiring may lead to a condition where the GFCI/RCD may NOT trip when it should, causing
electrical shock hazard. All electrical installations should be done by qualified personnel only.
Troubleshooting
Main electrical box
Warning!
Total current output cannot exceed total current input rating!
There are different
GFCI/RCD
models used on the market See manufacturer's instructions that come with the
GFCI/RCD
for specific information Note that all illustrations are examples only