Current time of segment (ramp or hold) in 

HH:MM or MM:SS (see time base)

Flashing LED when program is in RUN. LED on 

steady when program is in STOP, END,

HOLD and time base stopped.

Dynamic indication of segment (ramp or 

hold); off at the end of program

Flashing LED in modification phase

Flashing letter “P” in programmer state 

modification phase

N° of current step

N° of current program

EXAMPLE of programmer state display:  

Program = 2, Step = 5, Segment = Hold, time elapsed = 20:42 (MM:SS)

The setpoint can be changed directly from the keyboard only when the program is in STOP.

To change programmer state, press the “Lower” key for 2 seconds: the letter “P” will start flashing rapidly. Press key “F” to scroll: program, step, segment, 

time.

Flashing of the decimal point in each element indicates that the value is enabled for modification (“P” flashes slowly).

Use the “Raise” and “Lower” keys to set the required values. Press the “Lower” key for 2 seconds while “P” flashes rapidly or go to START to disable 

programmer state modification phase.

Program change automatically generates a reset.

Reset state is also entered by setting current step 0 (zero) and setting the current segment to “off” (lower right digit off).

8 • STATE OF THE PROGRAMMER

F

F

F

F

F

Level 1 display: 

programmer 

state

for 2 sec.

modify program

modify step

modify segment

modify time

Programmer 

modification phase

Restart with step search

The example shows a typical setpoint profile that can be programmed by setting a single 5-step program.  At start, if parameter Pty = 2 (in ProG), the 

program searches for the setpoint with value equal to PV.  The search is performed by moving the current time forward or backward, skipping phases or 

steps.  If the variable is lower than that required during a setpoint increase phase (point A, t1), at restart the current time base is lowered by intercepting the 

setpoint profile (point A1). 
If the variable is lower than that required during a setpoint decrease phase (point B, t2), 

at restart the current time base is raised by intercepting the setpoint profile (point B1). If 

interception is not possible, as in the case of variable at PV1, program restart occurs at the 

current time and setpoint. 

If the Hbb control is enabled, the programmer time base remains stopped until the variable 

re-enters the set tolerance band, symmetrically placed around the setpoint.

PV1

1

2

3

4

t1

t2

A1

A

B1

B

PV

/

Set point

Step 0

time

Display / Modification of programmer state

*

*

 

access 

granted only 

with program in 

STOP

In this mode, the maximum duration of a step is 30 seconds

In fast simulation mode, hold back band (Hbb) is inhibited, and control output takes on FAc.P value.

All other functions enabled (type of restart, start/stop, reset, manual/automatic, end of cycle or continuous cycle, event outputs, clearance from digital inputs, 

slave channel setpoint, etc.) are active.

- Autoreset means that programmer reset is active in Stop phase, with acquisition of the variable as current setpoint and resetting of time base.

- With the controller in manual or with absolute remote setpoint, the programmer time base is stopped.

- When switching from remote to local setpoint, the setpoint assumes the value of the remote setpoint at the time of switching.

Program control from panel:

In the absence of enabled digital inputs, alarms, M/A key (butt = 10, 11), program control engages when programmer state is displayed by using the Raise, 

Lower, and M/A keys.

Raise in stop = START; Lower in start = STOP; M/A pressed for 2 seconds = RESET (condition maintained with key pressed); Lower for 2 seconds in stop = 

enable change of programmer state.

When programmer state is not displayed, M/A key maintains function selected with “butt.”

Programmer Reset Mode:

With standard function, when the control is active the setpoint takes on the value of the process variable and power is forced to zero. 

When parameter “_ _ r.t.” is set to +16 and the reset control is active, the current setpoint (prior to reset) and power control are maintained. 

This function is applicable with reset from digital inputs or enabled keys, and also with reset following a program change (possible only in STOP) or from 

STOP/START switching at the end of a program.

11

80090G_MHW_1600-1800P_04-2013_ENG

Summary of Contents for 1600P

Page 1: ...range with or without decimal point PTC type on request DIN 43760 Pt100 JPT100 990Ω 25 C Max line resistance for RTD 20Ω Safety detection of short circuit or opening of probes LBA alarm HB alarm C F selection configurable from faceplate Linear scale ranges 1999 to 9999 with configurable decimal point position Thermocouples IEC 584 1 J K R S T B E N Ni Ni18Mo L NiCr CuNi Cold junction error 0 1 C C...

Page 2: ...r supply isolated 1500V 10 24Vdc max 30mA short circuit protection 9 5 18 20 19 21 22 Out2 AL1 Out1 Main C 32 W1 Transmitter supply GND Vt 1 2 3 4 5 6 7 8 9 10 11 24 25 26 27 28 29 30 31 32 33 22 21 20 19 18 17 16 15 14 13 12 1800 1600 NC NC NC NO NO NO C C PWR 3 1 2 T 3 1 2 T Key Function defined with but 2 parameter M A key Function defined with butt parameter PV Display Indication of process va...

Page 3: ...eep the F key pressed to scroll the menus Release the F key to select the displayed menu Press the F key to access the parameters Keep the F key pressed to exit any menu Keep F Auto Man keys pressed for 2 sec on any menu to go immediately to level 1 display S3 ON Current setpoint display only LEVEL 1 MENU PASS NO SI Hrd U CAL S4 ON YES NO Custom menu Password User calibration Protection code The a...

Page 4: ...ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON S step hold events Step S advanced through digital input function When digital inputs have state set in this function program automatically advances to next step otherwise it waits at end of previous step function is enabled through SP Pr parameter on Hrd menu d i F 1 and or d i F 2 set to 12 Hold Back Band value sy...

Page 5: ... control Ctrl 14 has been selected s tvn CFG Enabling self tuning autotuning softstart CFG Control parameters 15 S tun Continuos Self tuning Softstart autotuning 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 7 8 WAIT NO NO 9 GO NO NO 10 WAIT YES NO 11 GO YES NO 12 WAIT NO YES 13 GO NO YES Note 1 Active S tun functionS reset when switching from Automatic to Manual Propo...

Page 6: ...o local setpoint 2 digital absolute from serial line 3 digital relative to from serial line local setpoint PROBE TC SEnS 0 tYPE Probe type Scale Scale range max Scale range max C F without decimal point with decimal point 0 PTC 990Ω C 55 120 55 0 120 0 1 PTC 990Ω F 67 248 67 0 248 0 2 PTC 990Ω C Custom scale 3 PTC 990Ω F Custom scale tYPE Signal type Scale Max scale range 0 0 50mV linear 1999 9999...

Page 7: ...lla corrente di carico inferiore alla soglia impostata nel tempo di ON dell uscita di controllo 1 Uscita relè logica allarme attivo ad un valore della corrente di carico superiore alla soglia impostata nel tempo di OFF dell uscita di controllo 2 Allarme attivo se una delle funzioni 0 e 1 è attiva OR logico tra le funzioni 0 e 1 3 Per uscita continua di riscaldamento 7 Per uscita continua di raffre...

Page 8: ... analogue repetition signal output 2 Out W2 Assignment of signal or reference value PV SP SP PROG DEV DEV IN AUX HEAT COOL AL1 AL2 AL3 serial line value 79 80 81 Hrd sp pr hrd i hrd 2 Hrd Hardware configuration Installation of aux input digital inputs serial interface Installation of relay logic outputs MAIN AL1 AL2 AL3 and analogue outputs W1 W2 16 to enable analogue output W1 32 to enable analog...

Page 9: ...e 0 10V 2 10V 6 Custom 10V 7 Custom max 50mV Selection of probe type for main input 16 disable function in configuration menu only for butt parameters 8 to enable main input curve 4 point correction alternative to custom linearization See description in Main Input Correction Function section 16 to disable averaging filter on sampled value available from software release 3 05 8 to disable averaging...

Page 10: ...int value rPt ramp time from 0 0 to 99h59m time base in h m or 99m59s time base in m s set a time that gives a faster or slower variation depending on the initial value and on the final setpoint Sot hold time from 0 0 to 99h59m time base in h m or 99m59s time base in m s Hbb tolerance band symmetrically positioned above and below the setpoint and referenced to the main input or the auxiliary input...

Page 11: ...d by intercepting the setpoint profile point B1 If interception is not possible as in the case of variable at PV1 program restart occurs at the current time and setpoint If the Hbb control is enabled the programmer time base remains stopped until the variable re enters the set tolerance band symmetrically placed around the setpoint PV1 1 2 3 4 t1 t2 A1 A B1 B PV Set point Step 0 time Display Modif...

Page 12: ...he output is in OFF state The alarm is reset automatically when alarm conditions have been cleared If AL Hb is set at 0 both types of HB alarm are disabled and the assigned relay is de energized The load current reading is displayed by selecting InP2 level 1 NOTE ON OFF times refer to the cycle time set for the selected output Alarm Hb_F 3 7 for analog output is ON when the load current is lower t...

Page 13: ...ional band at 0 1 with on off type setting C Switch to automatic and observe the behavior of the variable It will be similar to that in the figure D The PID parameters are calculated s follows Proportional band Peak P B x 100 V max V min V max V min is the scale range Integral time It 1 5 x T Derivative time dt It 4 E Switch the unit to manual set the calculated parameters Return to PID action by ...

Page 14: ...mmer model the program is in STOP if self tuning is activated when the unit is switched on 14 SELF TUNING 15 AUTO TUNING PID parameters cannot be set if the self tuning function is enabled The function can be one of two types permanent or one shot The first continuously measures system oscillations to find the optimum PID values to reduce such oscillations It does not engage if the oscillations dr...

Page 15: ...n is applied to linear scales 50mv 10V 20mA Pot The four values are set on the Lin menu as follows A1 St100 B1 St01 A2 St02 B2 St03 Setting is limited to the defined scale LoS HiS on InP menu The offset function oFt parameter on InP menu remains enabled Limits B1 always greater than A1 B1 A1 at least 25 of full scale of selected probe Example Sens 9 TyPE 0 Pt100 natural scale 200 600 dPS 0 LoS 0 H...

Page 16: ...an isolation transformer be used only for the devices connecting the screen to ground it is important for the electrical system to have a good ground connection voltage between neutral and ground must not exceed 1V and resistance must be less than 6Ohm if the supply voltage is highly variable use a voltage stabilizer for the device use line filters in the vicinity of high frequency generators or a...

Reviews: