1 • INSTALLATION

• Dimensions and cut-out; panel mounting

Panel mounting:

Fix the device with the bracket provided before making any electrical 

connections.

To mount two or more devices side by side, use the cut-out dimensions 

shown above.

CE MARKINGThe instrument conforms to the European Directives 
2004/108/CE and 2006/95/CE with reference to the generic standards:

EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission 

in residential environment) EN 61010-1 (safety)

.

MAINTENANCERepairs must be done out only by trained and specialized 
personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, 
Trichlorethylene, etc.). Use of these solvents can reduce the mechanical 
reliability of the device. Use a cloth dampened in ethyl alcohol or water to 
clean the external plastic case.
SERVICEGEFRAN has a service department. The warranty excludes 
defects caused by any use not conforming to these instructions.

  4T 48

  UNIVERSAL TEMPERATURE  INDICATOR

SOFTWARE VERSION 3.2x

 (includes R77 version)

code 81600G / edition 13 - 07/2011

INSTALLATION and

OPERATION MANUAL

99

10

45

45

48

70

70

63
48

For correct and safe 

installation, follow 

the instructions and 

observe the warnings 

contained in this 

manual.

!

  Faceplate protection

  

IP65

  Working / Storage temperatures   0...50°C / -20...70°C

  Relative humidity   20 to 85%, non-condensing

  

Installation   Panel mounting, extractable from front

  Weight 

  

150g

 

  °C / °F selection   Faceplate configurable

  Linear scale ranges -1999...9999

Configurable decimal point position, 

possible 32 segment linearization

  Transmitter / Sensor Power

  Supply (option)

  24V ±10%, 50mA

  15V for transmitter, max. 50mA

  1,2V for potentiometer > 100Ω

  Fuse (inside device, not

 operator serviceable)

  100...240Vac - tipo T - 500mA - 250V

  11...27Vac/dc - tipo T - 1,25A - 250V

  Power supply (switching)

 (std) 100...240Vac/dc ±10%, 50/60Hz, 5,5VA

 (opt) 20...27Vac/dc ±10%, 50/60Hz, 5,5VA

  Max. non-linearity error   See t.P parameter

  Resolution

  (function of settable

sample time)

 120msec, >14bit - 16000 points

 60msec, >14bit - 16000 points 

 (only for linear inputs)

 30msec, >13bit - 8000 points 

 (only for linear inputs)

 15msec, >12bit - 4000 points

  (only for linear inputs)

  Thermocouples   J, K, R, S, T, B, E, N

  (IEC 584-1, CEI EN 60584-1, 60584-2)
  L GOST, U, G, D, C

  Custom linearization available on request

  Cold junction error   0,1° / °C

  RTD type  (scale configurable within 

 indicated range, with or without 

decimal point)

  

  Max. RTD line resistance

  

  DIN 43760 (PT100), JPT100

  

  20Ω

  PTC type / NTC type   990Ω, 25°C / 1KΩ, 25°C

Display 4 digit red LED’s; digit height 10mm,

  

Keys   3 mechanical keys (Raise, Lower, F)

  

Accuracy   0.2% f.s. at 25°C ambient temperature,

  ts=120msec

  Main input   TC, RTD, PTC, NTC

  60mV, 1V Ri ≥ 500KΩ; 5V, 10V Ri ≥10KΩ

  20mA, Ri = 50Ω

  adjustable digital filter

2 • TECHNICAL SPECIFICATIONS

   

FUNCTION 

  CABLE 

LENGTH USED

 TC input probe   

0,8 mm

2

 compensated   5 m

 “PT100” input probe  

1 mm

2

  

3 m

Power supply cable  

1 mm

2

  

1 m

EMC conformity has been tested with the following connections

  Environmental conditions of 

use   for internal use only, altitude up to 2000m

Logic input

(only R77 version)

24V, 5mA (Ri = 47KΩ) isolation 1500V 

or voltage-free contact

1

81600G_MHW_4T48_07-2011_ENG

                               1 / 7

Summary of Contents for 4t-48

Page 1: ...election Faceplate configurable Linear scale ranges 1999 9999 Configurable decimal point position possible 32 segment linearization Transmitter Sensor Power Supply option 24V 10 50mA 15V for transmitt...

Page 2: ...arameter to be raised or lowered The speed of change is proportional to the time the key is pressed The operation is not cyclic once the maximum minimum limit is reached there will be no further incre...

Page 3: ...n display Input settings Pressed for approx 2 sec Keep the F key pressed to browse the menus Release the F key to enter the displayed menu Press the F key to access the parameters Keep the F key press...

Page 4: ...0 120 0 33 PTC F 67 248 67 0 248 0 34 NTC C 10 70 10 0 70 0 35 NTC F 14 158 14 0 158 0 Probe Voltage Current 36 0 60mV 1999 9999 199 9 999 9 37 0 60mV custom linear custom linear 38 12 60mV 1999 9999...

Page 5: ...tP TC CUSTOM U C CPU T Function 2 Custom RTD sensor 3 Custom PTC sensor 4 Custom NTC sensor 5 Potentiometer 0 to 1V Digital filter on main input Digital filter on process variable display 0 0 to 20 0...

Page 6: ...not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires shoul...

Page 7: ...Gefran 4T 48 Installation Manual Temperature Indicator Tel 27 0 43 743 9471 sales industrialthermal co za 91 Currie Street Quigney East London 5200 Powered by TCPDF www tcpdf org...

Reviews: