N.B.: for the version R77 are not available the probe codes 0...39, 48...51, 54...58

In case of probe non-availability, maximum and minimum limits are set to 0.

In case of custom linearization, test limits for setting LO and HI errors are given by the calibration values.

If these limits are not exceeded, they are taken into consideration as limits L_S and H_S.

Select sampling time 

(resolution). For linear 

input 0...1V/POT only.

  0  120ms  > 14bit; 16000 divs

  1  60ms 

> 14bit; 16000 divs

  2  30ms 

> 13bit; 8000 divs

  3  15ms 

> 12bit; 4000 divs

 TYPE  Type 

4 DIGIT

   

PROBE

   

 

without dec. point  with dec. point

  Probe: TC

  0 

TC J °C 

0/1000 

0.0/999.9

  1 

TC J °F 

32/1832 

32.0/999.9

  2  TC K °C 

0/1300 

0.0/999.9

  3  TC K °F 

32/2372 

32.0/999.9

  4  TC R °C 

0/1750 

0.0/999.9

  5  TC R °F 

32/3182 

32.0/999.9

  6  TC S °C 

0/1750 

0.0/999.9

  7  TC S °F 

32/3182 

32.0/999.9

  8  TC T °C 

-200/400 

-199.9/400.0

  9 

TC T °F 

-328/752 

-199.9/752.0

 10  TC B °C 

44/1800 

44.0/999.9

 11  TC B °F 

111/3272 

111.0/999.9

 12  TC E °C 

-100/750 

-100.0/750.0

 13  TC E °F 

-148/1382 

-148.0/999.9

 14  TC N °C 

0/1300 

0.0/999.9

 15  TC N °F 

32/2372 

32.0/999.9

 16  TC L °C 

0/600 

0.0/600.0

 17  TC L °F 

32/1112 

32.0/999.9

 18  TC U °C 

-200/400 

-199.9/400.0

 19  TC U °F 

-328/752 

-199.9/752.0

 20  TC G °C 

0/2300 

0.0/999.9

 21  TC G °F 

32/4172 

32.0/999.9

 22  TC D °C 

0/2300 

0.0/999.9

 23  TC D °F 

32/4172 

32.0/999.9

 24  TC C °C 

0/2300 

0.0/999.9

 25  TC C °F 

32/4172 

32.0/999.9

 26 

TC °C 

Custom 

Custom

 27 

TC °F 

Custom 

Custom

  Probe: RTD

 28  PT100 °C 

-200/600  

-199.9/600.0

 29  PT100 °F 

-328/1112 

-199.9/999.9

 30  JPT100 °C 

-200/600  

-199.9/600.0

 31  JPT100 °F 

-328/1112 

-199.9/999.9

    Probe: PTC - NTC

 32  PTC °C 

-55/120   

-55.0/120.0

 33  PTC °F 

-67/248   

-67.0/248.0

 34  NTC °C 

-10/70   

-10.0/70.0

 35  NTC °F 

14/158   

14.0/158.0

    Probe: V Current

 36  0...60mV 

-1999/9999 

-199.9/999.9

 37  0...60mV 

custom linear 

custom linear

 38  12...60mV 

-1999/9999 

-199.9/999.9

 39  12...60mV  custom linear 

custom linear

 40  0...20mA 

-1999/9999 

-199.9/999.9

 41  0...20mA 

custom linear 

custom linear

 42  4...20mA 

-1999/9999 

-199.9/999.9

 43  4...20mA 

custom linear 

custom linear

  44  0...10V 

-1999/9999 

-199.9/999.9

 45  0...10V 

custom linear 

custom linear

 46  2...10V 

-1999/9999 

-199.9/999.9

 47  2...10V 

custom linear 

custom linear

 48 

0...5V 

-1999/9999 

-199.9/999.9

 49 

0...5V 

custom linear 

custom linear

 50 

1...5V 

-1999/9999 

-199.9/999.9

 51 

1...5V 

custom linear 

custom linear

 52  0...1V/Pot 

-1999/9999 

-199.9/999.9

 53  0...1V/Pot  custom linear 

custom linear

 54  200mV...1V  -1999/9999 

-199.9/999.9

 55  200mV...1V  custom linear 

custom linear

    Probe: Custom   PT100 - PTC - NTC

 56 

PT100 

custom   

custom

   

JPT

 57 

PTC 

custom   

custom

 58 

NTC 

custom   

custom

• TC/LIN input parameters

Input settings

Type of probe, 

signal and scale of 

main input

+4 to disable filter

(average of the last eight values sampled)

Max. non-linearity error for

thermocouples (TC),

resistors (PT100) and

thermistors (PTC, NTC).

The error is calculated as

deviation from theoretical value

and is expressed as percentage of full 

scale (in °C).

 S, R  range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other range; error < 0.5% f.s.

 T 

error < 0.2% f.s. (t > -150°C)

 B 

range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range 44,0...999,9; error < 1% f.s. (t > 300°C)

 U 

range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other range; error < 0.2% f.s. (t > -150°C)

 G 

error < 0.2% f.s. (t > 300°C)

 D 

error < 0.2% f.s. (t > 200°C)

 C 

range 0...2300; error < 0.2% f.s. / for other range; error < 0.5% f.s.

 NTC  error < 0.5% f.s.

 Tc JKENL 

error < 0.2% f.s.

 PT100, JPT100 e PTC 

error < 0.2% f.s.

In

t.P

(.1.

4

81600G_MHW_4T48_07-2011_ENG

                               4 / 7

Summary of Contents for 4t-48

Page 1: ...election Faceplate configurable Linear scale ranges 1999 9999 Configurable decimal point position possible 32 segment linearization Transmitter Sensor Power Supply option 24V 10 50mA 15V for transmitt...

Page 2: ...arameter to be raised or lowered The speed of change is proportional to the time the key is pressed The operation is not cyclic once the maximum minimum limit is reached there will be no further incre...

Page 3: ...n display Input settings Pressed for approx 2 sec Keep the F key pressed to browse the menus Release the F key to enter the displayed menu Press the F key to access the parameters Keep the F key press...

Page 4: ...0 120 0 33 PTC F 67 248 67 0 248 0 34 NTC C 10 70 10 0 70 0 35 NTC F 14 158 14 0 158 0 Probe Voltage Current 36 0 60mV 1999 9999 199 9 999 9 37 0 60mV custom linear custom linear 38 12 60mV 1999 9999...

Page 5: ...tP TC CUSTOM U C CPU T Function 2 Custom RTD sensor 3 Custom PTC sensor 4 Custom NTC sensor 5 Potentiometer 0 to 1V Digital filter on main input Digital filter on process variable display 0 0 to 20 0...

Page 6: ...not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires shoul...