• WARNINGS

ORDER CODE

Read the following warnings before installing, connecting or using the device:

• follow instructions precisely when connecting the device.

• always use cables that are suitable for the voltage and current levels indicated in the technical specifications.

• the device has no ON/OFF switch: it switches on immediately when power is turned on. For safety reasons, devices permanently connected to the 

power supply require a two-phase disconnecting switch with proper marking. Such switch must be located near the device and must be easily reachable 

by the user. A single switch can control several units.

•  if  the  device  is  connected  to  electrically  NON-ISOLATED  equipment  (e.g.  thermocouples),  a  grounding  wire  must  be  applied  to  assure  that  this 

connection is not made directly through the machine structure.

• if the device is used in applications where there is risk of injury to persons and/or damage to machines or materials, it MUST be used with auxiliary alarm 

units. You should be able to check the correct operation of such units during normal operation of the device. 

• before using the device, the user must check that all device parameters are correctly set in order to avoid injury to persons and/or damage to property.

• the device must NOT be used in inflammable or explosive environments. It may be connected to units operating in such environments only by means of 

suitable interfaces in conformity to local safety regulations.

• the device contains components that are sensitive to static electrical discharges. Therefore, take appropriate precautions when handling electronic circuit 

boards in order to prevent permanent damage to these components.

Installationinstallation category II, pollution level 2, double isolation

The equipment is intended for permanent indoor installations within their own enclosure or panel mounted enclosing the rear housing and exposed terminals on the back.

• power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the 

device label.

• install the instrumentation separately from the relays and power switching devices

• do not install high-power remote switches, contactors, relays, thyristor power units (particularly if “phase angle” type), motors, etc... in the same cabinet.

• avoid dust, humidity, corrosive gases and heat sources.

• do not close the ventilation holes; working temperature must be in the range of 0...50°C.

If the device has faston terminals, they must be protected and isolated; if the device has screw terminals, wires should be attached at least in pairs.

• Power: supplied from a disconnecting switch with fuse for the device section; path of wires from switch to devices should be as straight as possible; the 

same supply should not be used to power relays, contactors, solenoid valves, etc.; if the voltage waveform is strongly distorted by thyristor switching units 

or by electric motors, it is recommended that an isolation transformer be used only for the devices, connecting the screen to ground; it is important for the 

electrical system to have a good ground connection; voltage between neutral and ground must not exceed 1V and resistance must be less than 6Ohm; 

if the supply voltage is highly variable, use a voltage stabilizer for the device; use line filters in the vicinity of high frequency generators or arc welders; 

power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the 

device label.

• Input and output connections: external connected circuits must have double insulation; to connect analog inputs (TC, RTD) you have to: physically 

separate input wiring from power supply wiring, from output wiring, and from power connections; use twisted and screened cables, with screen connected 

to ground at only one point; to connect adjustment and alarm outputs (contactors, solenoid valves, motors, fans, etc.), install RC groups (resistor and 

capacitor in series) in parallel with inductive loads that work in AC (Note: all capacitors must conform to VDE standards (class x2) and support at least 220 

VAC. Resistors must be at least 2W); fit a 1N4007 diode in parallel with the coil of inductive loads that operate in DC.

GEFRAN  spa  will  not  be  held  liable  for  any  injury  to  persons  and/or  damage  to  property  deriving  from  tampering,  from  any  incorrect  or 

erroneous use, or from any use not conforming to the device specifications.

!

WARNING: this symbol indicates danger.

It is seen near the power supply circuit and near high-voltage relay contacts.

Please, contact GEFRAN sales people for the codes availability.

For T input (alternative to RTD, PTC, NTC)

 1,2Vdc for potentiometer (*)

0 1

 15Vdc for transmitter

1 5

TRANSMITTER POWER SUPPLY

 None

0 0

 100 to 240Vac/dc

1

POWER SUPPLY

 11 to 27Vac/dc

0

 24Vdc, 50mA

2 4

 (*) R77 for version with potentiometer input (Rinput > 10MΩ)

4T

48

4

NR. DIGITS

 4 

4

6

81600G_MHW_4T48_07-2011_ENG

                               6 / 7

Summary of Contents for 4t-48

Page 1: ...election Faceplate configurable Linear scale ranges 1999 9999 Configurable decimal point position possible 32 segment linearization Transmitter Sensor Power Supply option 24V 10 50mA 15V for transmitt...

Page 2: ...arameter to be raised or lowered The speed of change is proportional to the time the key is pressed The operation is not cyclic once the maximum minimum limit is reached there will be no further incre...

Page 3: ...n display Input settings Pressed for approx 2 sec Keep the F key pressed to browse the menus Release the F key to enter the displayed menu Press the F key to access the parameters Keep the F key press...

Page 4: ...0 120 0 33 PTC F 67 248 67 0 248 0 34 NTC C 10 70 10 0 70 0 35 NTC F 14 158 14 0 158 0 Probe Voltage Current 36 0 60mV 1999 9999 199 9 999 9 37 0 60mV custom linear custom linear 38 12 60mV 1999 9999...

Page 5: ...tP TC CUSTOM U C CPU T Function 2 Custom RTD sensor 3 Custom PTC sensor 4 Custom NTC sensor 5 Potentiometer 0 to 1V Digital filter on main input Digital filter on process variable display 0 0 to 20 0...

Page 6: ...not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires shoul...

Page 7: ...Gefran 4T 48 Installation Manual Temperature Indicator Tel 27 0 43 743 9471 sales industrialthermal co za 91 Currie Street Quigney East London 5200 Powered by TCPDF www tcpdf org...

Reviews: