Replace AGy-L by VDL200
Pag. 13 of 17
5 VDL200 Commissioning
This chapter explaines the corispondence of the parameters in AGy-L and the ones in VDL200. If the parameter in AGy-L are not
retrievable anylonger, set directly the VDL200 parameters based on the data available (speed, motor data, encoder etc…).
5.1 Set motor parameters in STARTUP WIZARD menu
Copy AGy-L PAR into
VDL200 PAR
AGy-L
VDL200
S.100
PAR 2000
S.150
PAR 2002
S.101
PAR 2004
S.001
PAR 2006
S.151
PAR 2008
not
available
(*)
PAR 2010
S.152
PAR 2012
(*) Set the value reported on the plate of the motor into VDL200 PAR: 2010.
03 STARTUP WIZARD
Set motor data?
E=Yes
Down=Next
E
SEQ
01
PAR: 2000
Rated voltage
400
V
Def:
400
E
SEQ
01
PAR: 2000
Rated voltage
00000040
0
v
Def:
400
401 V
399 V
E
SEQ
02
PAR: 2002
Rated current
11.8
A
Def:
11.8
E
SEQ
02
PAR: 2002
Rated current
00000011.
8
A
Def:
11.8
11.9 A
11.7 A
E
SEQ
03
PAR: 2004
Rated speed
1450
rpm
Def:
1450
E
SEQ
03
PAR: 2004
Rated speed
000000145
0
rpm
Def:
1450
1451 rpm
1449 rpm
E
SEQ
04
PAR: 2006
Rated frequency
50
Hz
Def:
50
E
SEQ
04
PAR: 2006
Rated frequency
00000005
0
Hz
Def:
50
51 Hz
49 Hz
E
SEQ
05
PAR: 2008
Pole pairs
2
Def:
2
E
SEQ
05
PAR: 2008
Pole pairs
2
Def:
2
3
1
E
SEQ
06
PAR: 2010
Rated power
5.50
kW
Def:
5.50
E
SEQ
06
PAR: 2010
Rated power
0000005.5
0
kW
Def:
5.50
5.51 kW
5.49 kW
E
SEQ
07
PAR: 2012
Rated power factor
0.83
Def:
0.83
E
SEQ
07
PAR: 2012
Rated power factor
0.8
3
Def:
0.83
0.84
0.82
E