81906_MAN_GRP-H_02-2022_ENG_pag. 55
5.3.3.
Process data mapping
The device has the following Process Data Input mapping:
Word n
Meaning
Offset
Length
6
Actual output power Ou.P (
Percentage value of
delivered power)
)
96
16 bit
5
Load current Ld.A (
RMS load current
)
80
16 bit
4
Load voltage Ld.V (
Load voltage
)
64
16 bit
3
Load power Ld.P (
Power on load
)
48
16 bit
2
Load impedance Ld.I (
Load impedance
)
32
16 bit
1
STATUS2
Bit 6..15= Not used
Bit 5=
STATUS2_NO_CURRENT
Bit 4=
STATUS2_NO_VOLTAGE
Bit 3=
STATUS2_SSR_SHORT
Bit 2=
(*)
Bit 1=
STATUS2_HB
Bit 0=
(*)
16
16 bit
0
STATUS3
Bit 14..15= Not used
Bit 13=
STATUS3_CURRENT_SENSOR_BROKEN
Bit 5..12= Not used
(**)
Bit 4=STATUS3_FREQUENCY_WARNING
Bit 2..3=
(**)
Bit 1=
STATUS3_SCR_OVER_HEAT
Bit 0=
STATUS3_SCR_TEMP_SENSOR_BROKEN
0
16 bit
(*) Bits not published in the IODD file but still available.
Bit 0 OR of Bit 1, Bit 2
Bit 2 Power Fault (OR of Bit 3,4,5)
(**) Bits not published in the IODD file but still available.
Bit 2 Phase soft start on
Bit 3 Phase soft start end
Bit 5 50Hz (0) / 60Hz (1)
The device has the following Process Data Output mapping:
Position
Meaning
Offset
Length
0…15
Output power Man.P (Percent value of manual
power to be supplied) (*)
0
16 bit
(*) The power value delivered by the static group GRP is updated starting from the PDO when the mode is
OPERATE. In the other modes (SIO, STARTUP, PREOPERATE) the value is not updated (the last value set
remains).
During operation in IO-Link the value of the PDO Man.P is NOT saved in the retentive memory.
At start-up, the Man.P value is restored to the default value (equal to Man.P = 0.0%).