background image

PROFILE
The GT family of solid-state relays has
been designed with the aim of providing
very accurate control of the load thanks
to an analog control input, in voltage at
0…5V; 0…10V or in current at
0…20/4…20mA or a potentiometer (from
1K

to 10 K

).

The electronic design ensures that the
cycle time for proportioning the power is
automatically optimized.
Il numero di periodi che il GT fornisce al
carico (“treni d’ onda”) per un certo
valore di segnale di ingresso, è calcolato
in modo da essere il minimo possibile,
pur mantenendo la precisione
necessaria.
The number of cycles that the GT
supplies to the load (wave trains) for a
given input signal is calculated to be the
minimum possible to maintain the
necessary accuracy.
The GT can be used in three phase
systems, using master-slave control
architecture in which the control signal
drives only one GT (master) and this unit
supplies the synchronized signals to the
other slaves. Two GS modules can also
be used as slaves (logic control).
A load interrupt control option (HB) is
available without having to use an
external current transformer; alarm limit

is settable with trimmer and yellow LED
signal, with voltage-free contact, normally
open.
The GT solid-state relay has a green
LED to indicate the presence of the
24Vac power supply and a red LED to
indicate the switching based on the
analog control input signal.
The LED signal will be continuous (off at
minimum, on at maximum) at the ends of
the scale, pulsing for intermediate
values.
The units offer optional accessoires for
panel mounting, fuses and fuseholders,
current transformer,  isolation
transformers.
Use the relè with an opportune heatsink
(see section accessories).

TECHNICAL DATA

General features

Category of use AC1
Nominal voltage
- 480Vac (max. range 24...530Vac)
Nominal frequency: 50/60Hz
Non-repetitive voltage: 1200Vp
Zero switching voltage: 

20V 

Voltage drop at nominal current

1.4Vrms 

Power factor = 1

Control inputs

Voltage: 0...5Vdc, 0...10Vdc 
(impedance 

100K

)

Current: 0...20mA, 4...20mA
(impedance 125

)

Potentiometer: da1K a 10K

(auto-fed by GT)

O

UTPUTS

GT 25 (SCR version)

Nominal currents of the device with
opportune heatsink in continuous work:
25A
Non-repetitive overcurrent t=20 ms: 400A
I

2

t for blowout: 

645A

2

s

dV/dt critical with output deactivated:
1000V/µs

GT 40 (SCR version)

Nominal currents of the device with
opportune heatsink in continuous work:
40A

GT 25 / 40 / 50 / 60 / 75 / 90 / 120A

SOLID STATE RELAYS WITH ANALOG CONTROL

Main features

• Command input from analogue voltage

or current signal or potentiometer.

• Switching at voltage zero crossing.
• Partialization of wave train power with 

dynamically optimized time cycle.    

• Antiparallel double SCR
• 2 led for supply indication, “ON” state,

1 optional LED for load interrupt alarm

• 4000V isolation between input circuit 

and power output 

• MOV (varistor)
• Optional monitoring of interrupted load

Main applications

• Plastics extrusion lines

and injection moulding 
machines

• Polymerization plant for

synthetic fibre production

• Rubber moulding 

machinery

• Driers for ceramics and 

components for the
building industries

• Chemical and 

pharmaceutical industries

• Industrial electric furnaces
• Food processing plants

Summary of Contents for GT 120A

Page 1: ...ermediate values The units offer optional accessoires for panel mounting fuses and fuseholders current transformer isolation transformers Use the rel with an opportune heatsink see section accessories...

Page 2: ...h junction ambient 12 K W Solid State Relay Dissipated Power Calculation Singol phase static relay Pds 1 4 IRMS W IRMS singol phase load current Heatsink thermal resistance Calculation Rth 90 C T amb...

Page 3: ...ifferent cycle times 100msec and 40msec respectively V V Example of input at 20 2V IN 0 10V or 4mA IN 0 20mA V Voltage across load Example of input at 50 5V IN 0 10V or 10mA IN 0 20mA V Voltage across...

Page 4: ...ge for potentiometer power supply 10V 24 Vac 50 60 Hz power terminal The solid state power unit Gt is supplied factory calibrated for 0 5V 0 10V 0 20mA 4 20mA 10Kohm potentiometer Minimum and maximum...

Page 5: ...ther 1 10 of a turn 1 notch on the scale In this way the alarm limit is set below 10 of the rated load current N B the partial load break alarm function operates with power partialization exceeding 15...

Page 6: ...PLES L2 h L1 i Master AL PWR Line 230 V GT 25A 480 Vac e Max Adj d Min Adj c Reset Alarm f Input selection g Alarm Adj Line 30 Vdc ac ON 2 Out Alarm 1 Slave 3 Line 480 V 0 10V 0 20mA 4 20mA 0 5V AC1 5...

Page 7: ...6 7 8 10 Vdc 24 Vac Supply Out Input Analog 1 2 3 Out 30 Vdc ac Alarm Master Slave ON PWR AL 4 20mA d Min Adj AC1 50 60 Hz GT 25A 480 Vac 0 20mA c Reset Alarm L1 h i L2 0 5V 0 10V Load Line 480 V f In...

Page 8: ...th neutral Controller Relay output Alarm solid state relay Digital output 0 20mA 4 20mA 0 10Vdc 0 5Vdc Three phase connection triangle or star without neutral with control of two phases using one GT i...

Page 9: ...es thermostats current transformers and isolation transformers To choose accessories see the section Solid state relays Accessories Fuse Fuse Fuse TABLE OF TERMINALS AND CONDUCTORS 25 40A 6 3x9 Eye fo...

Page 10: ...y from dust humidity corrosive gases and heat sources The connection cable must be shorter than 3 meters if the current transformer is used Maintenance Check the correct operation of the cooling fans...