2
80118_MHW_R-ECAT_08-2021_ENG
GEFRAN spa
via Sebina, 74 - 25050 Provaglio d’Iseo (BS)
Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.com
3 • TECHNICAL DATA
Power supply
- Supply with class 2 device
- 24 VDC ±25% 2A max., powers the entire GILOGIK II system
- Polarity inversion protection and short-circuit protection.
Ethernet
- Standard RJ45 - IN connection
- Standard RJ45 - OUT connection
- Number two rotary switches x01 and x10 for “Explicit Device Value”
setting of the slave
Diagnostics
- Yellow POWER led: power supply on
- Green RUN led:
INIT: steady off
PREOP: flashing slowly
SAFEOP: single flash with pause
OP: steady on
- Red ERROR led:
OFF: no errors
CONTINUOUS FLASHING: configuration error
SINGLE FLASH: generic runtime error
DOUBLE FLASH: watchdog on cyclic data
- Yellow LINK led: network connected
- Green ACTIVITY led: data transfer
Mechanical data
Dimensions: 92x90x25,4mm
Weigth: 150g.
Fixing: snaps onto R-BUS(x)
Protection level: IP20
Ambient Conditions
Working Temperature: 0...50°C
Storage Temperature: -20...70°C
Humidity: max. 90% Rh not condensing
For UL: Maximum surrounding air temperature 50°C
4 • CONNECTIONS
5 • WEEE INFORMATION
Pursuant to Article 26 of Italian Legislative Decree no. 49 of
14 March 2014 “Implementation of Directive 2012/19/EU on
waste electrical and electronic equipment (WEEE)”.
The symbol showing a crossed-out wheeled bin on equipment or its
packaging indicates that the product must be collected separately
from other waste at the end of its useful life.
The manufacturer is responsible for organising and managing the
separate collection of this piece of equipment at the end of its useful
life.
Users wishing to dispose of the equipment must therefore contact the
manufacturer to obtain instructions from the same on how to have the
equipment collected separately at the end of its useful life.
By collecting the disused equipment separately, it can be recycled,
treated or disposed of in an environmentally friendly manner, thus
helping to prevent the environment and public health from being af-
fected negatively and enabling reuse and/or recycling of the materials
forming the same equipment.
(*) Use shielded category 5E cable. In any case, for higher categories, always
use shielded cable.
Normally use straight cable for IN / OUT connection.
(**) Use unipolar cable with 1-1.5mm cross section.
The module installs on
R-BUS(x) in the first slot on
the left.
1
8
8
1
yellow POWER led
green RUN led
red ERROR led
green
ETHERCAT IN led
yellow LINK
ETHERCAT IN led
green ACTIVITY
ETHERCAT OUT led
yellow LINK
ETHERCAT OUT led
Product release
RJ45 ETHERCAT IN (*)
RJ45 ETHERCAT OUT (*)
Power supply (**)
24V DC ± 25% max 2A
Explicit Device Identification
Tens:
0..9 = 0..90
A = 100
B = 110
C = 120
D = 130
E = 140
F = 150
Explicit Device Identification
Units:
0..9 = 0..90
A , B, C, D, E, F = do not use:
reserved functions