R-U16
MODULE WITH 16 DIGITAL OUTPUTS
cod. 80120C / Edit 04 - 08/09 - ENG
INSTALLATION AND OPERATION MANUAL
2 • INSTALLATION AND CONNECTION
This section contains the instructions necessary for correct
installation of the GILOGIK II into the machine control panel
or the host system and for correct connection of the system
power supply, inputs, outputs and interfaces.
Before proceeding with installation read the following
warnings carefully!
Remember that lack of observation of these warnings
could lead to problems of electrical safety and electroma-
gnetic compatibility, as well as invalidating the warranty.
Qualified staff
the installation and use of the system and components are only reserved
at qualified staff.
Conform use
the system and relative components are usable exclusively to the use
previewed in the manual
In order to guarantee a correct and sure operation are indispensable that
the product comes transported, stored correctly, installed, and controlled
second the previewed modalities.
Suitable for use in pollution degree 2 environment.
Open type equipment
Notes Concerning Electrical Safety and Electromagnetic
Compatibility:
• CE MARKING: EMC Conformity (electromagnetic compatibility)
in accordance with EEC Directive 2004/108/CE. The GILOGIK II
system is mainly designed to operate in industrial environments,
installed on the switchboards or control panels of productive process
machines or plants.
Norm of applicable product EN 61131-2.
The Declaration of conformity is available on GEFRAN web:
www.gefran.com
• UL listed standard: UL508 file E198546
• BT Conformity (low tension)
in accordance with Directive LVD 2006/95/CE.
Advice for Correct Installation for EMC
Inputs and outputs connection
• The externally connected circuits must be doubly isolated.
• To connect the analogue inputs the following is necessary:
- physically separate the input cables from those of the power supply, the
outputs and the power connections.
- use woven and screened cables, with the screen earthed in one point
only.
GEFRAN S.p.A. declines all responsibility for any damage
to persons or property caused by tampering, neglect,
improper use or any use which does not conform to the
characteristics of the controller and to the indications
given in these Instructions for Use.
I
1 • MAIN FEATURES
• 16 2A max. outputs
• Short-circuit and overload protection on all outputs
• Diagnostics LED for power supplies, outputs and alarm
• Power supply to 24 VDC ± 25% outputs
• Removable connector supplied
80120C_MHW_R-U16_0809_ENG
I
3 • TECHNICAL DATA
- Controls 16 optically isolated 24VDC digital outputs
- Organization: 1 group of 2 outputs
2 groups of 4 outputs
- Maximum voltage of output power supply 32V
- Maximum current for output 2A
- Maximum current for group of 8 outputs 8A
- Maximum current for group of 4 outputs 6A
- Maximum current for 16 outputs 15A
- Current protection for output > 2.2A
- Current protection for group of 8 outputs > 10 A
- Isolation > 2KV
- Overvoltage on output for 1ms max.1KV
- Power supply via backplane R-BUS(x) 3.3V
- For UL: supply with class 2 device
Diagnostics
• Yellow LED presence 24V power supply
• Green LED for each output
• Red LED module in alarm
M
ECHANICAL DATA
Dimensions: 92x90x25,4mm
Weight: 120 g. max
Attachment: snaps onto R-BUS(x)
Protection level: IP20
Connector: front 20 pin