12. Setting of the end stops
General information
The end positions are set via the 12V SELV circuit of the device.
For setting the end positions of the RESCUEline drives, only a special potential-free setting
switch can be used.
Learning can only be started via the programming button or the limit switch and the DOWN key.
H
Attention danger to life: When connecting a usual setting switch with
mains connection, the 12V SELV circuit is connected under mains
voltage.
Article number / GEIGER setting switch
M56F155
with service terminal (D), 5 wires
I
Important: please observe the connecting diagram on the back of the
setting switch.
Factory setting
• The motor is set on the lower end position at the factory. The upper end stop is at the very
other end (at least lower end stop + 200 motor rotations).
• The motor command is in normal operation.
• The referencing is enabled on delivery.
✎
Note: If the motor is installed in a closed Venetian blind and if the
limit stop switch is used the motor can be operated without further
settings.
I
If the factory setting has been carried out and if the programming
mode is activated, max. 100 revolutions can be done downwards.
Reset to factory settings for a further run downwards.
13. Activate the programming mode
I
Prerequisite: The motor is positioned between the upper and the
lower end position. The limit stop switch should not be pressed.
Activate the programming mode
via limit stop switch
Press the programming key of the setting switch until, after
about 3 seconds, the motor confirms “end position
programming activated” with 1 x click-clack. Then release
the key.
Activate learning mode on the electronic
control unit
Press the limit stop switch and also press the DOWN key
on the locked Venetian blind switch.
The motor moves for 1 second.
Keep both keys pressed for another 3 seconds. The motor
confirms with a short movement downwards.
1 x
Press programming
key for about
3 seconds
Click-clack
PROG
PROG
Press key
+