background image

Optional Surge Suppression 

 
 
The SP, SVR, and VSS Series PDUs 

include a surge suppression circuit that 
is designed to prevent voltage surges on 

the input power line from reaching 
devices powered by the PDU.  The surge 

suppression circuit uses Metal Oxide 
Varistors (MOVs) connected between 

Line, Neutral, and Ground wires to 
prevent voltage surges from damaging 
connected devices.     

 
 

Surge Protection Circuit Ratings 

Protection Voltage  

330 V (Line-Line, Line-Neutral, Neutral-Ground) 

 
Energy Absorption 

720 Joules 

 

Green Light Indicator 

Power On  

 

Red Light Indicator 

Surge Protection Active  

 

 
 

GM1001.doc 

14 

Revision Date: 3/25/2009 

 

Summary of Contents for BR Series

Page 1: ...Geist Manufacturing 1821 Yolande Ave Lincoln NE 68521 800 432 3219 402 474 3400 F 402 474 4369 www geistmfg com Instruction Manual Rack Power Distribution Unit BR SP SVR VRT NSV and VSS Series ...

Page 2: ...structions 5 Guidelines 5 Mounting 6 Optional Surge Suppression 14 Surge Protection Circuit Ratings 14 Optional Local Monitoring 15 Power Meter 15 Current Meter 15 Service Tech Support 16 Service and Maintenance 16 More Technical Support 16 Table of Figures 17 Revision History 18 Revision History 18 GM1001 doc 2 Revision Date 7 1 2009 ...

Page 3: ...le in horizontal configurations rated 125 V All PDU Series covered by this instruction sheet can optionally be configured with a Geist Power Meter that provides local monitoring and display of Current Voltage Wattage and Power Factor Environmental Temperature Operating 10 C 50 F min 45 C 113 F max Storage 25 C 13 F min 65 C 149 F max Humidity Operating 5 min 95 max non condensing Storage 5 min 95 ...

Page 4: ...2 this device must accept any interference received including interference that may cause undesired operation This Class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada Warning Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to ope...

Page 5: ...ve on over current protection and supply wiring The PDU relies on the building installation for protection from over current conditions A Listed circuit breaker is required within the building installation The circuit breaker should be sized according to the PDU s nameplate ratings and local national electrical codes Reliable earthing of rack mount equipment should be maintained Particular attenti...

Page 6: ...Mounting Full Length Bracket Using the full length bracket mount PDU to rack as shown Mini L Brackets SLB 4 Using the mini L brackets attach PDU to rack as shown GM1001 doc 6 Revision Date 7 1 2009 ...

Page 7: ...on brackets attach PDU to rack as shown Toolless Mounting Hardware 11621 Secure toolless mounting buttons to PDU as shown Use toolless buttons with key holed slots built into cabinet or with optional Geist key holed brackets GM1001 doc 7 Revision Date 3 25 2009 ...

Page 8: ...h toolless bracket and toolless mounting buttons attach PDU to rack as shown Single Side Mount 2 Unit Brackets TSMX2 Using single side mount 2 unit brackets and toolless mounting buttons attach PDU to rack as shown GM1001 doc 8 Revision Date 3 25 2009 ...

Page 9: ...de Mount Brackets EZB 1 Using the offset side mount brackets attach PDU to rack as shown 7 Extension Brackets XB 7 Using the 7 extension brackets attach PDU to rack as shown GM1001 doc 9 Revision Date 3 25 2009 ...

Page 10: ...ush Mount Brackets FM Using flush mount brackets attach PDU to rack as shown Adjustable Mount Brackets AM Using adjustable mount brackets attach PDU to rack as shown GM1001 doc 10 Revision Date 3 25 2009 ...

Page 11: ... Brackets PM Using panel mount brackets attach PDU to rack as shown 23 Conversion Mounting Brackets 23 RM Using conversion mounting brackets attach 19 PDU to 23 rack as shown GM1001 doc 11 Revision Date 3 25 2009 ...

Page 12: ...ach cable mount bracket to PDU as shown use tie wraps to secure cords to bracket 19 Horizontal Panel Mount Brackets 7938 Using the 19 horizontal panel mount brackets attach PDU to rack as shown GM1001 doc 12 Revision Date 3 25 2009 ...

Page 13: ...ing Clips 9083C 9084C Using the top and bottom mounting clips attach the PDU to the rack as shown Please note that mounting clips are only intended for use with NSV and VSS Series PDUs GM1001 doc 13 Revision Date 3 25 2009 ...

Page 14: ...he surge suppression circuit uses Metal Oxide Varistors MOVs connected between Line Neutral and Ground wires to prevent voltage surges from damaging connected devices Surge Protection Circuit Ratings Protection Voltage 330 V Line Line Line Neutral Neutral Ground Energy Absorption 720 Joules Green Light Indicator Power On Red Light Indicator Surge Protection Active GM1001 doc 14 Revision Date 3 25 ...

Page 15: ...PDU output voltage measured in true RMS Voltage Power PDU output power measured in Watts referred to as real or active power Power Factor Ration of real PDU output power to apparent PDU output power2 Power Meter Display Current Meter The Geist CM 1 current meter is a low power high accuracy meter capable of measuring true RMS Current The value of current is continuously shown on an easy to read 4 ...

Page 16: ...e PDU or you may void the warranty No serviceable parts inside It is recommended that power be removed from the unit before installing or removing any equipment More Technical Support http www geistmfg com 800 432 3219 Email support geistmfg com Or contact your distributor GM1001 doc 16 Revision Date 7 1 2009 ...

Page 17: ...TLFL 8 Single Side Mount 2 Unit Brackets TSMX2 8 Offset Side Mount Brackets EZB 1 9 7 Extension Brackets XB 7 9 Flush Mount Brackets FM 10 Adjustable Mount Brackets AM 10 Panel Mount Brackets PM 11 23 Conversion Mounting Brackets 23 RM 11 Cable Mount Bracket CMB 1 12 19 Horizontal Panel Mount Brackets 7938 12 Top and Bottom Mounting Clips 9083C 9084C 13 Power Meter Display 15 Current Meter Display...

Page 18: ...GM1001 doc 18 Revision Date 3 25 2009 Revision History Revision Date Notes Approved By 1 0 3 26 2009 Original Published Version JLP ...

Reviews: