Upgradeable PDU Instruction Manual
30
© 2017 Geist
GM1157
Chapter 3 - Setup
Interchangeable Monitoring Device
The Interchangeable Monitoring Device (IMD) is the core behind the Geist Upgradable line of power
products. The IMD can be replaced and upgraded to allow data-centers to future-proof their locations.
Basic
The Basic Geist Upgradable PDU is the baseline for the GU line of products. It is built with the IMD-
01
X module, and provides low cost power distribution with the option to upgrade to add local metering
and/or remote monitoring and other features in the future.
Metered
The Metered Geist Upgradable PDU is a locally metered option for the GU line of products. It is built
with the IMD-
01
D module, and provides a local display for viewing current draw (Amps) and power
(Kilowatts), with the option to upgrade to add monitoring and other features in the future.
Figure 3-1
IMD-
01
D Module
1.
Local Display
: The local display will display the phase, line, and circuit current values (in Amperes).
2.
Display Buttons
: There are three buttons near the IMD display; a back button, a forward button, and
a center button. The functions of these buttons are as follows:
Back Button
Decrement to the previous channel.
Forward Button
Increment to the next channel.
Center Button
Toggle between scrolling and static display modes. Holding this button
for 10 seconds will perform a network reset, restoring the default IP
address and resetting user account information.