19
No.
Faults
Origin
Elimination
Power reduction because
Only partial loading possible
of situating in the height
Excessive environment temp.
The gas-electric generating sets
are designed for an environment
temperature up to 40°C
7
The aggregate turns off but can
The overtemperature breaker
See No. 6
again be started after cooling
of the gas-electric generating
set is actuated
It is forbidden to change the installations of the adjusting screws marked with red varnish. Otherwise, all guarantees are cancelled. If defects repeat, it is necessary to address to the manufacturer or an aut-
horized workshop (see the list of the authorized workshops in the Appendix). Mount only original components when replacing them.
14. Scheduled
maintenance
Before the beginning of maintenance works, the engine should be stopped.
14.1 Electric components
The generator does not require maintenance. It is only necessary to periodically clean the case from dust to
avoid the worsening of cooling conditions.
14.2 Engine
The screw of regulating the quality of the mixture, rotation-frequency regulator, and throttle valve restrictor
are sealed with red varnish. It is forbidden to disturb adjustments, because the generator and consumers
can be damaged.
14.2.1 Check of the fuel tank and fuel guides
* Check the fuel tank and fuel guides on tightness and the absence of damages.
* Check the condition of the thread of the fuel-tank cover.
* Clean components from pollution.